background image

The Ductless Split System of Choice

Made in Rome, New York, USA

7

• Re-test the oil after 48 hours. If acid is still present,

install a new suction drier. If acid is not present, re-

move suction drier.

EVAPORATOR COIL FREEZE-UPS

If your EMI indoor coil freezes in the straight cooling

mode, it is probably caused by one of the following:

• System undercharge

• Very low primary voltage

• Stuck compressor contacts

• Refrigeration circuit restriction

• Incorrect expansion device (too restrictive)

• Very low indoor load (low indoor temperature)

• Airflow problem (defective motor, plugged filter, unit

blocked by curtains, furniture, etc.)

• Low ambient cooling without low ambient controls.

If the system is asked to cool indoor space while out-

door space is consistently below 60° F, the system must

be  fitted  with  low  ambient  components.  For  these

cases, EMI offers an optional low ambient field in-

stalled kit.

NOTE:

 EMI technical service can help you di-

agnose problems with your unit(s). Feel free

to call us Monday through Friday from 8am-

5pm at (315) 336-3716.

CHILLED WATER PIPING (WCP/CCP/FCP)

Standard connections provided are sweat type. See

specifications for  line size and actual unit connections.

NOTE:

 Water pipe sizes are given in I.D.

• Use pipe unions or compression fittings to aide fu-

ture service. Use isolation valves to aide in unit re-

moval.

• Connections can be brazed or soft-soldered.

• 

Follow manufacturer’s instructions for any field

installed control valves.

• 

Unit control is provided for a 24v normally closed/

power open valve.

NOTE:

 Consult factory if other types of valves

are used.

• Insulate supply and return piping with closed cell

foam tube insulation.

• Avoid necessary bends.

• Avoid kinks by using a tubing bender.

•  Make  sure  glycol  solution  is  compatible  with  all

valves, unions, and compression fittings. Ethylene or

propylene is recommended.

• Bleed air from system prior to start-up. Units are

equipped with a standard air bleeder on the highest

point of the unit piping.

CAUTION:

 Disconnect power when bleeding

system. Make certain liquid does not contact

any electrical components.

Finish all piping before balancing the system. Bleed

system, adjust temperature and/or water flow rate until de-

sired results are achieved.

The unit filter must be in place and able to be removed

easily for maintenance. To avoid vibration, check chilled

water lines to ensure they are not in contact with each other.

The unit(s) must be mounted securely and level. (See

 In-

stallation, Operation & Maintenance Guide

 for complete

instructions.)

WSP/WHP  &  FSP/FHP  UNIT  MOUNTED

ELECTRONIC  CONTROLS (FEATURES)

• Large 3/4" LCD Display

• Operational range adjustable between 55°and 90° F

in 1.0° increments

• Anti-Short Cycle Compressor Protection

• Fan Purge (fan remains on for 60 seconds after heat/

cool call is dropped for improved efficiency)

• Indoor Coil Freeze Protection (available in Straight

Cool, Cooling Only With Optional Electric Heat, Cool/

Heat Pump With Electric Strip Heat, and Two Stage

Heating).

• Fan Operation (Auto, High, Low)

Auto Fan Operation-

 Automatically selects fan speed

according to heating or cooling demand.

Constant Fan Operation-

 Manually selected High

or Low Speed.

• Optional Hand Held Infrared Controller (a separate

Hand Held Remote used to command the Onboard

Controls).

• Test Operation (allows ease of unit testing after in-

stallation by eliminating all timers).

DIPSWITCH SETTINGS

Dipswitches are located in the control section on the

universal relay board. They must be set according to the unit

application (i.e., straight cool, electric heat, heat pump).

The dipswitches must be set prior to installation and

before either the indoor or outdoor units are connected to

power (use the following table as a guide).

Sw itch

1

2

Cooling Only

off

off

Cool/Electric Heat

on

on

All Heat Pumps

off

on

Summary of Contents for AmericaSeries LLC-09

Page 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Page 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Page 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Page 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Page 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Page 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Page 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Page 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Page 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Page 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Page 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Page 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Page 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Page 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Page 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Page 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Page 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Page 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Page 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Page 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Page 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Page 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Page 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Page 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Reviews: