background image

The Ductless Split System of Choice

Made in Rome, New York, USA

3

approximately 20 seconds. At that point the unit will enter

defrost mode for approximately 2 seconds. During this time

the condenser fan will switch off, the reversing valve will

energize  and  the  defrost  board  will  energize  the  indoor

electric heat relay through the “W” terminal. After the 2

second defrost cycle is complete, the unit will switch back

to heating operation for another twenty seconds. This process

will repeat until the jumpers are removed from the test pins.

NOTE:

 If the condenser coil is heavily frosted

with ice, it is likely that the “Defrost Sensor” is

already closed so the “R and DFT” jumper can

be eliminated. To initiate defrost, momentarily

jump “DFT TST” until the defrost cycle begins

but DO NOT leave the jumper in place. The

unit  will  remain  in  defrost  mode  until  the

condenser  coil  is  defrosted  and  will  then

resume heating mode.

L

IMITED

 R

ANGE

 H

EAT

 P

UMP

 A limited range heat pump is a model that does not

utilize a defrost sequence in heating mode since this unit

will  not  operate  during  periods  of  outdoor  temperatures

below 35° F.

The EMI limited range heat pumps are designed to

cease operation at 35° F. (+/- 3° F) and automatically switch

into electric resistance or hydronic heating only, as long as

the evaporator has been supplied with supplemental heat

from the factory (it is recommended that supplemental heat

be ordered as an option with ALL heat pump evaporators).

The specific control that is used to monitor the extreme

cold conditions and break power to the compressor is called

a Changeover Thermostat (“C.O. T’stat” on wire diagram).

This  device  has  a  long  sensing  bulb  on  its  body  that  is

strategically  placed  from  the  factory  for  best  sensing

capability.

The  EMI  MH2  &  MH4  series  condensers  are

manufactured  as  limited  range  heat  pumps.  The

capacities available range from 9,000 BTU/h up to 30,000

BTU/h nominal capacity.

MIXING  &  MATCHING  EQUIPMENT  IN  A

SPLIT SYSTEM (STRAIGHT COOL ONLY)

It is possible to mate EMI air handlers and condensing

units with other manufacturers’ products in 

Straight Cool

Applications

 if the following conditions are met properly

(see EMI Policy Bulletin #910503).

• All equipment capacities must have the same BTU/h

rating and efficiency rating (SEER).

• A transformer must be added to the outdoor unit if

not standard.

• If a thermostat is not supplied by EMI it must have

an independent “G”signal capability to operate the fan.

• EMI must test and/or approve any non-EMI equip-

ment if heat pump applications require manufacturer

mixing.

NOTE:

 If EMI equipment is installed in a mixed

equipment system without prior approval, EMI

will void ALL warranties.

GENERAL WIRING PROCEDURES

EMI systems require the following electrical wiring

for proper operation:

• 24v transformer (standard in all EMI condensers).

NOTE:

 It may be necessary to install a trans-

former if using another manufacturer’s straight

cool condenser (see “Mixing & Matching Equip-

ment” in this guide.)

• Indoor and outdoor unit high-voltage supply and ac-

companying wiring must match unit specifications.

• If optioned, low voltage thermostat wiring must run

between  the  indoor  and  outdoor  units  (also  wall-

mounted thermostat NEC class II wiring).

EMI 

AmericaSeries

 condensers are designed to oper-

ate with EMI 

AmericaSeries 

evaporators. Both the condenser

(outdoor unit) and evaporator (indoor unit) have a 

high volt

service connection and are intended to be independently con-

nected to the electrical service panel (see the unit name plate

for correct breaker types and sizes).

The outdoor and indoor units are also connected to

each other through 

low volt

 interconnect wiring. A 24v trans-

former located in the condensing unit provides the low volt

power source.

The control circuit operates on a 24v a/c power sup-

ply. Control of the condenser is provided either by the

indoor evaporator unit or a wall mounted remote ther-

mostat.

For example, Model SHC condensing units are de-

signed to independently connect to a high volt power supply

(see name plate for required voltage and circuit breakers).

The high volt connection is made through three 6-inch lead

wires located in the control section (refer to wiring diagram).

Wiring connections must abide by NEC and any local elec-

trical codes.

Low volt connections are made through the 5-posi-

tion terminal located in the control section. This circuit is an

NEC Class-II low volt circuit. The low volt terminal block

is labeled C, Y, O, W2, and R.

Summary of Contents for AmericaSeries LLC-09

Page 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Page 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Page 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Page 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Page 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Page 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Page 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Page 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Page 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Page 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Page 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Page 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Page 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Page 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Page 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Page 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Page 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Page 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Page 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Page 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Page 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Page 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Page 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Page 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Reviews: