background image

10

EMI Products are subject to ongoing development.

Products & Specifications may change without notice.

H

EATING

This unit is designed to utilize two-stage heating. The

first stage being the compressor and the second electric heat.

The air handler will cycle the condenser on and off through

the yellow (Y) wire as it does in cooling; however; the re-

versing valve will 

not

 be energized. To check for a con-

denser signal:

Step 1-

 Place the indoor unit in heating mode with the

Mode

 button.

Step 2-

 Using the 

Up

 arrow, place the setpoint tem-

perature one degree above room temperature.

Step 3-

 With a voltmeter, check for 24 volts across the

yellow  (Y)  and  brown  (C)  wires. The electric heat

should be off at this point.

Step 4-

 With the 

Up

 arrow, select a setpoint tempera-

ture that is more than two degrees above the room tem-

perature. The electric heat should energize along with

the 24v compressor signal between Y and C. Check to

see that the amp draw corresponds with the electric

heat rating.

The following current values apply when the unit is

connected to a 230v power supply. These values include fan

motor current:

3kw (13.5 amps)

4kw (18 amps)

5kw (22.3 amps)

Units with electric heat have a strip heater located be-

hind the evaporator coil. The control relay for the heater in

located on the circuit board in the control box. A limit switch

located on the heater end plate will interrupt power to the

heater should the airflow become compromised. If  tempera-

tures rise above the limit, setting a non-resetting one-time

fuse link will burn and the heater will remain off.

U

NITS

 

WITH

 C

ONDENSATE

 P

UMPS

Models WSP or WHP are available with an optional

condensate  pump.  Condensate  pumps  are  recommended

when it is not possible to gravity drain the condensation from

the indoor unit. The condensate pump is located behind the

front control panel and has a maximum lift capability of 4

feet from the base of the unit.

NOTE:

  Condensation  generated  by  the

evaporator will collect in the pump reservoir.

When the water level is high enough, a float

switch  will  close  and  energize  the  pump,

clearing the water from the reservoir. Should,

for any reason, the water exceed the maximum

preset level, a secondary float will open a safety

switch, thereby cutting the (Y) signal to the

condenser.  This  will  prevent  the  evaporator

from  generating  more  condensation  and

spilling out of the unit.

FREEZE PROTECTION

The indoor fan coil unit is protected in the event of

freeze up. If the evaporator falls below 32° F for more than

three minutes, the compressor is forced off.  When the evapo-

rator temperature returns to 50° F,  normal cooling opera-

tion resumes. If the evaporator returns to above 32° F but

remains below 50° F for 10 minutes, cooling operation will

also resume.

OPERATIONAL MODES

- Fan only

- Cooling only

- Cooling with optional indoor electric strip heat

- Cooling/Heatpump with optional electric strip heat

O

N

/O

FF

 S

WITCH

The 

On/Off

 switch is used to turn the equipment on or

off. In the 

Off

 mode, the LCD will be blank and all LED

indicator lights will be dark. To turn the unit on press the

On/Off

 button once. The LCD will display the room tem-

perature and LED indicators will light up to show fan speed

and mode selection.

I

NITIAL

 S

TARTUP

Upon initial power-up the unit will start in 

Fan

 only

mode at 

High

 speed. These are the default settings of the

microprocessor. Once temperature and mode selections have

been made, they will be stored in the microprocessor memory

when  the  unit  is  switched  off. The  next  time  the  unit  is

switched back on via the 

On/Off 

switch, the stored settings

will be used and the unit will resume operation. If power is

lost, the equipment will return to an 

Off 

state (if it was on)

and any temperature or mode settings will be lost.

M

ODE

 S

WITCH

 (S

YSTEM

 S

WITCH

)

The 

Mode 

button will allow the selection of the de-

sired mode. Colored LED indicators will light next to the

selected mode. With each successive press of the 

Mode

 but-

ton, selection will rotate between 

Heat, Cool

 and 

Fan

. There

is a 7 second time delay after the mode button is released

before the execution of the selection to prevent the unit from

starting prematurely.

F

AN

 O

PERATION

These units utilize a two-speed motor with three op-

erational fan modes. The 

Fan

 button will allow the selec-

tion of the desired fan mode. With each successive press of

the 

Fan

 button, selection will rotate between 

High, Low,

 and

Auto

. In 

Fan

 mode, 

Auto

 is bypassed and only 

High

 or 

Low

are available. An amber LED indicator will light next to the

fan speed selection. If 

Auto

 fan speed is selected then an

LED indicator will also light next to 

Auto

High

 and 

Low

selections are constant fan settings.

Summary of Contents for AmericaSeries LLC-09

Page 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Page 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Page 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Page 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Page 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Page 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Page 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Page 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Page 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Page 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Page 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Page 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Page 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Page 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Page 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Page 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Page 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Page 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Page 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Page 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Page 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Page 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Page 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Page 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Reviews: