background image

6

EMI Products are subject to ongoing development.

Products & Specifications may change without notice.

COMPRESSOR REPLACEMENT

Before replacing the compressor, test it to make sure

it is defective. Check the complete electrical system to the

compressor and its internal electrical system to be sure that

it is not out on internal overload. Reset the manual high pres-

sure switch (if equipped with one).

A complete evacuation of the system must be made

whenever you have a defective compressor or suspect it may

be. If the compressor has been operating for some time, a

careful analysis must be made to determine why the com-

pressor failed.

Many compressor failures are caused by the fol-

lowing conditions:

• Poor initial installation of the system.

• Changes to the system after installation.

• Improper airflow over the evaporator.

• Overcharged refrigerant system causing liquid to be

returned to the compressor.

• Restricted refrigerant system.

• Lack of lubrication (horizontal and excess tubing

must be sloped towards the compressor).

• Lack of p-traps in risers.

• Liquid refrigerant returning to compressor causing

oil to be washed out of bearings.

• Non-condensables such as air and moisture in the

system. Moisture is extremely destructive to a refrig-

erant system.

• Acid present in a sealed system.

R

ECOMMENDED

 P

ROCEDURE

 

FOR

 C

OMPRESSOR

 R

EPLACEMENT

• Perform all necessary electrical and refrigeration tests

to be sure the compressor is actually defective before

replacing the compressor.

• Be sure power source is off and disconnect all wir-

ing at compressor.

• Capture (reclaim) all refrigerant.

• After all refrigerant has been captured, disconnect

suction as discharge lines from the compressor and

remove compressor. Be certain to have both suction

and liquid line gauge ports and/or process tube open

to atmosphere.

• Disconnect both liquid and suction line connections

at the unit and inspect inside the fittings for any for-

eign particles that may have collected there.  (The for-

eign particles can consist of pieces of valves, wind-

ings, or thermal overload particles, and other related

items normally located within the compressor shell.)

• If any foreign particles are present, they must be re-

moved.

• Carefully capture a small amount of oil from the de-

fective compressor by pouring from the compressor.

NOTE:

  It  is  not  possible  to  pour  oil  from  a

rotary type compressor. On rotary compressor

systems, oil must be collected from the system

tubing after properly recapturing refrigerant.

• Use an acid test kit (one-shot or conventional kit) to

test the oil for acid content according to the instruc-

tions with the kit.

• If any evidence of a burnout is found, no matter how

slight, the system should be flushed with nitrogen.

• Replace the liquid line filter drier if you have a com-

pressor burnout.  It is recommended that the next larger

filter drier be installed and a suction filter drier be

added, following instructions in the filter drier sec-

tion.

REMEMBER:

 Remove the suction line drier

after a few days of continuous operation.

• Install the replacement compressor.

• Pressurize with nitrogen and leak test all connec-

tions with a leak detection fluid (i.e., soap). Discharge

nitrogen and repair any leaks found. Repeat until all

leaks are repaired.

• Evacuate the system with a vacuum pump capable

of a final vacuum of 200 microns. The system should

be evacuated through both liquid and suction lines and

gauge ports. While the unit is being evacuated, seal

all openings on the defective compressor. Compres-

sor manufacturers will void warranties on received

units that are not properly sealed. Do not distort the

manufacturer’s tube connections.

• Recharge the system with the correct amount of re-

frigerant. Use an accurate measuring device, such as

a charging cylinder, electronic scales, or similar de-

vice, if necessary. It is necessary to add additional re-

frigerant to compensate for the volume of the driers

for a basic system charge. See “Charging the System”

in this manual.

Summary of Contents for AmericaSeries LLC-09

Page 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Page 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Page 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Page 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Page 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Page 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Page 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Page 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Page 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Page 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Page 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Page 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Page 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Page 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Page 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Page 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Page 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Page 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Page 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Page 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Page 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Page 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Page 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Page 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Reviews: