background image

The Ductless Split System of Choice

Made in Rome, New York, USA

5

fan on the high pressure side of the system.

• Multiple compressor units also utilize a single cyling

condenser fan on the high pressure side of the system.

The operating range is 210-275 psi. This enables cool-

ing down to approximately 0° F.

NOTE:

 Multiple compressor units use one (1)

fan for all of the compressors.

 Heat Pump- 

The low ambient option is available on

single zone heat pump systems. These units also utilize a

single cycling condenser fan, with a relay that allows the

fan to run continuously in heating mode.

• Multiple compressor heat pump units use a hot gas

bypass method. The system uses an automatic expan-

sion valve (AXV) to prevent coil freeze up. This al-

lows hot gas to bypass to the suction side under low

ambient conditions.

L

OW

 A

MBIENT

 T

ROUBLESHOOTING

If the condenser motor cycles rapidly or does not op-

erate at all, check for the following:

• Power to the motor

• Total  system  undercharge-  System  cannot  obtain

minimum pressures to signal the motor to cycle (refer

to STG for charging information)

• If the unit is charged properly and operating under

low ambient conditions (65° dry bulb F or lower), the

motor should cycle rapidly between 210 (motor off)

and  275 (motor on) psi on the high side.

• If the outdoor temperatures coincide with EMI sys-

tem performance charts (65° F and above), in most

cases, the motor will run continuously. In some cases,

under normal operating conditions the motor may have

periods when it will cycle in the 65-75° F temperature

range. This is not abnormal and is not cause for alarm.

CONDENSATE PUMPS & DRAIN

EMI recommends one trap (required on the TBC/TBH

models)  for  the  drain  line  after  it  leaves  the  unit.  Never

double trap the drain line. Pour water into the drain pan af-

ter installation to ensure proper drainage.

• When installing the condensate line, make certain

the  unit  is  not  installed  at  a  distance/height  that  is

greater than the capability of the factory installed pump

(see  “Pump  Specifications”).  EMI  factory  installed

pumps have a maximum lift of 4 feet from the bottom

of the unit.

NOTE:

  Before  completing  installation,  test

pump action.

• EMI offers external pumps for installations that re-

quire more than 4 feet of lift.

SYSTEM TROUBLESHOOTING

If your EMI system does not seem to operate prop-

erly, or  the pressure/temperature readings are not correct,

refer to this section and the “Troubleshooting Guide” in this

manual. Run through the following checklist to properly di-

agnose a problem with your EMI system.

• Is the unit switched on?

• Are the controls calling for heat or cool?

• Is the evap fan running properly?

• Is the condenser fan running properly?

• Is condenser air flow adequate and unrestricted?

• Is the compressor running?

• Is subcooling excessive? (see explanation below)

• Is superheat too high/low? (see explanation below)

• Is the supplied voltage  for the unit correct and

within normal tolerances?

Excessive subcooling

 is caused by non-condensables

(air/water), overcharge, dirty coil, or a restriction. Purge and

draw vacuum to determine if non-condensables are the prob-

lem. If it doesn’t solve the problem, remove refrigerant until

subcooling is no longer excessive. If the system was over-

charged, this will solve the problem. If it does not solve the

problem, check superheat readings.

WARNING!!  It  is  illegal  to  discharge

refrigerant  into  the  atmosphere.  Use

proper reclaiming methods & tools when

installing or servicing equipment.

High superheat 

is caused  by an undercharge, leak,

or restriction. If refrigerant is added to the system to nor-

malize subcooling and the superheat is still high, then there

is a restriction (possible underfeeding expansion device). If

superheat is no longer high, the system was undercharged.

Locate any leaks and repair. When no leaks are found or

remain, recharge the system.

Low superheat (floodback)

 is caused by an over-

charge, overfeeding expansion device, or inefficient com-

pressor. If refrigerant is removed and both subcooling and

super heat readings are normal, the system was overcharged.

Check the efficiency of the compressor if subcooling is low.

If the compressor is normal, the expansion device is over-

feeding.

NOTE:

 Condensing units built before January

1, 1994, require the service panel be placed

over the service opening when performing tests

to get true readings.

Summary of Contents for AmericaSeries LLC-09

Page 1: ...the side and 48 to the front and rear be GENERAL INFORMATION This guide is intended for use by EMI contractors distributors installers representatives and service technicians to gain a better underst...

Page 2: ...ndenser is equipped with low ambient fan control for cooling The fan will remain off while in cooling mode until the condenser pressure reaches 275psi The fan will then energize and run until the cond...

Page 3: ...ng conditions are met properly see EMI Policy Bulletin 910503 All equipment capacities must have the same BTU h rating and efficiency rating SEER A transformer must be added to the outdoor unit if not...

Page 4: ...ave a P trap installed at the base to facilitate oil return when the condenser is above the evaporator Fig 1 When the evaporator is installed above the compres sor the trap will prevent the flow of li...

Page 5: ...ft of 4 feet from the bottom of the unit NOTE Before completing installation test pump action EMI offers external pumps for installations that re quire more than 4 feet of lift SYSTEM TROUBLESHOOTING...

Page 6: ...ct inside the fittings for any for eign particles that may have collected there The for eign particles can consist of pieces of valves wind ings or thermal overload particles and other related items n...

Page 7: ...ession fittings Ethylene or propylene is recommended Bleed air from system prior to start up Units are equipped with a standard air bleeder on the highest point of the unit piping CAUTION Disconnect p...

Page 8: ...NTRO L B AT T E R IE S INCL UDE D POWER ON OFF Button INFRA RED SENSOR T EMP SET POINT DOWN Button T EMP SET POINT UP Button LCD Display HEAT OPERAT ION Indicator FAN LOW Indicator FAN HIGH Indicator...

Page 9: ...Y wire When the air handler is calling for cooling 24v can be measured between terminals wires Y and C NOTE Most condenser manufacturers do not supply low volt transformers with their condensers When...

Page 10: ...ereby cutting the Y signal to the condenser This will prevent the evaporator from generating more condensation and spilling out of the unit FREEZE PROTECTION The indoor fan coil unit is protected in t...

Page 11: ...ton in Place the setpoint tem perature above the room temperature The compressor will start heating and run as long as the setpoint is above the room temperature Some EMI heat pump condensers are equi...

Page 12: ...ar may not work for a unit manufactured in a dif ferent model year NOTE EMI does not stock or recommend electric heat add on kits for field installation It is critical that if you can foresee the need...

Page 13: ...______________________________________ Subcooling ___________________________________________________________ Suction Temperature at Compressor _____________________________________ Voltage Running __...

Page 14: ...a F e g r a h C m e t s y S l a t o T 2 1 W C L z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 0 3 z o 3 3 z o 6 3 z o 3 4 LCC 12 p a v E l e d o M e n i L T F G H C e n i L h t g n e L t f l a t o T t...

Page 15: ...r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C P S C 2 1 P H W P S W 2 1 P H F P S F 2 1 H C B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 z o 3 1 z o 5 6 2 z o 9 2 z o 2 3 z o 9 3 p a v E l...

Page 16: ...L t f l a t o T t s u j d A y r o t c a F e g r a h C m e t s y S l a t o T 2 1 P H C 2 1 P H F 2 1 P H W 2 1 H B T 2 1 H A C z o 5 2 0 1 5 2 0 5 z o 3 z o 6 3 1 z o z o 2 4 z o 5 4 z o 8 4 z o 5 5 S...

Page 17: ...e g r a h C m e t s y S l a t o T 4 2 P H C P S C 4 2 P H F P S F 4 2 P H W P S W 4 2 H C B T 4 2 H A C 6 5 0 1 5 2 0 5 z o 6 z o 4 1 z o 8 2 z o 1 4 z o 7 4 z o 5 5 z o 9 6 MH 18 l e d o M p a v E e...

Page 18: ...5 1 1 0 8 2 0 2 2 5 7 5 7 1 5 6 2 0 6 2 5 2 1 5 2 2 0 0 2 0 8 0 7 1 0 6 2 0 6 2 5 2 1 5 8 1 0 8 1 5 8 0 6 1 5 5 2 0 4 2 5 2 1 5 8 1 0 6 1 0 9 5 5 1 5 4 2 0 3 2 0 1 1 5 4 1 0 6 1 5 9 0 5 1 5 4 2 0 2 2...

Page 19: ...in Degrees F p m e T D O F s e e r g e D 9 0 2 1 5 1 8 1 4 2 0 3 6 3 5 6 5 4 3 5 8 2 0 1 2 5 9 1 5 4 2 0 2 2 0 3 2 0 7 0 7 2 0 7 2 0 1 2 0 9 1 0 4 2 5 3 2 0 3 2 5 7 5 1 2 0 6 2 0 1 2 0 9 1 0 4 2 0 4...

Page 20: ...20 EMI Products are subject to ongoing development Products Specifications may change without notice O L Over Load...

Page 21: ...ump Pending Slv Brg Whl C 265V 60Hz E X Special 220 240V 50Hz F A Standard 0 Standard B No Expansion KW X Special C Open 208V 230V 265V D Open NONE 0 0 Unit Mount w Trans Mechanical E Aeroquip 2 50 3...

Page 22: ...C 1 2 D A 0 0 0 0 A A 0 A A SCC C Straight Cool 0 Standard SHC H Heat Pump A Z A Standard 9 000 BTU 09 A Standard 12 000 BTU 12 X Special 15 000 BTU 15 0 Painted Coil No Grille Std 115V 60Hz A A Coat...

Page 23: ...____________________________________________ __________________________________________________________________________________________ ________________________________________________________________...

Page 24: ...almaintenance Damage or repairs required as a consequence of faulty installation or application by other Failure to start due to voltage conditions blown fuses open circuit breakers or other damages d...

Reviews: