240
Unidrive M702 User Guide
Issue Number: 3
Ensure cables used suit local wiring regulations.
Table 12-18 Cable ratings (200 V)
Table 12-19 Cable ratings (400 V)
NOTE
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input
Output
Input
Output
Nominal Maximum
Nominal Maximum
Nominal Maximum
Nominal Maximum
03200050
1.5
4
1.5
4
14
10
14
10
03200066
03200080
4
4
12
12
03200106
04200137
6
8
6
8
10
8
10
8
04200185
8
8
8
8
05200250
10
10
10
10
8
8
8
8
06200330
16
25
16
25
4
3
4
3
06200440
25
25
3
3
07200610
35
70
35
70
2
1/0
2
1/0
07200750
1
1
07200830
70
70
1/0
1/0
08201160
95
2 x 70
95
2 x 70
3/0
2 x 1
3/0
2 x 1
08201320
2 x 70
2 x 70
2 x 1
2 x 1
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG
Input
Output
Input
Output
Nominal Maximum
Nominal Maximum
Nominal Maximum
Nominal Maximum
03400025
1.5
4
1.5
4
18
10
18
10
03400031
16
16
03400045
14
14
03400062
2.5
2.5
03400078
03400100
12
12
04400150
6
8
6
8
10
8
10
8
04400172
8
8
8
8
05400270
6
6
6
6
8
8
8
8
05400300
06400350
10
25
10
25
6
3
6
3
06400420
16
16
4
4
06400470
25
25
3
3
07400660
35
70
35
70
1
1/0
1
1/0
07400770
50
50
2
2
07401000
70
70
1/0
1/0
08401340
2 x 50
2 x 70
2 x 50
2 x 70
2 x 1
2 x 1/0
2 x 1
2 x 1/0
08401570
2 x 70
2 x 70
2 x 1/0
2 x 1/0
CAUTION