Unidrive M702 User Guide
223
Issue Number: 3
11.21.6 Slot 4 Menu 15: Modbus
Parameter
Range
Default
Type
OL
RFC-A
RFC-S
OL
RFC-A
RFC-S
4.15.001
Enable
Off (0) or On (1)
On (1)
RW
Bit
US
4.15.002
Reset
Off (0) or On (1)
Off (0)
RW
Bit
4.15.003
Default
Off (0) or On (1)
Off (0)
RW
Bit
4.15.004
Modbus Configuration Error
No error (0), Port in use (1),
Timeout event (2)
RO
Txt
4.15.005
Modbus Listening Port
0 to 65535
502
RW
Num
4.15.006
Maximum Connections
0 to 4
2
RW
Num
US
4.15.007
Maximum Priority Connections
0 to 4
1
RW
Num
US
4.15.008
Maximum Connections Per Client
1 to 4
2
RW
Num
US
4.15.009
Modbus Timeout
1 to 10000 ms
100 ms
RW
Num
US
4.15.010
Modbus Timeout Action
Trip (0), No action (1)
No action (1)
RW
Txt
US
4.15.011
Modbus Timeout Event Destination
This slot (0), Slot 1 (1), Slot 2 (2), Slot 3 (3), Slot 4 (4)
This slot (0)
RW
Txt
US
4.15.012
Modbus Timeout Event Type
No event (0), Trigger Event (1), Trigger Event 1 (2),
Trigger Event 2 (3), Trigger Event 3 (4),
Trigger Event 4 (5)
No event (0)
RW
Txt
US
4.15.013
Modbus Register Addressing Mode
Standard (0), Modified (1)
Standard (0)
RW
Txt
US
4.15.020
Priority Connection 1
0.0.0.0 to 255.255.255.255
0.0.0.0
RW
IP
US
4.15.021
Priority Connection 2
0.0.0.0 to 255.255.255.255
0.0.0.0
RW
IP
US
4.15.022
Priority Connection 3
0.0.0.0 to 255.255.255.255
0.0.0.0
RW
IP
US
4.15.023
Priority Connection 4
0.0.0.0 to 255.255.255.255
0.0.0.0
RW
IP
US
RW
Read / Write
RO
Read only
Num
Number parameter
Bit
Bit parameter
Txt
Text string
Bin
Binary parameter
FI
Filtered
ND
No default value
NC
Not copied
PT
Protected parameter
RA
Rating dependent
US
User save
PS
Power-down save
DE
Destination
IP
IP address
Mac
Mac address
Date
Date parameter
Time Time parameter
SMP Slot,menu,parameter
Chr
Character parameter
Ver
Version number
Summary of Contents for Unidrive M702