Unidrive M702 User Guide
269
Issue Number: 3
Slot4 HF
Ethernet interface in slot 4 hardware fault
250
The
Slot4 HF
trip indicates that the Ethernet interface in slot 4 on the drive has detected an error. The reason for the error
can be identified by the sub-trip number.
Recommended actions:
•
Hardware fault - Contact the supplier of the drive.
Slot4 Not Fitted
Ethernet interface in slot 4 has been removed
253
The
Slot4 Not Fitted
trip indicates that the Ethernet interface in slot 4 on the drive has been removed since the last power-
up.
Recommended actions:
•
Hardware fault - Contact the supplier of the drive.
Slot4 Watchdog
Ethernet interface watchdog service error
251
The
Slot4 Watchdog
trip indicates that the Ethernet interface installed in slot 4 has started the option watchdog function and
then failed to service the watchdog correctly.
Recommended actions:
•
Hardware fault - Contact the supplier of the drive.
Slot App Menu
Application menu Customization conflict error
216
The Slot App Menu trip indicates that more than one option slot has requested to customize the application menus 18, 19
and 20. The sub-trip number indicates which option slot has been allowed to customize the menus.
Recommended actions:
•
Ensure that only one of the Application modules is configured to customize the application menus 18, 19 and 20
SlotX Different
Option module in option slot X has changed
204
209
214
The
SlotX Different
trip indicates that the option module in option slot X on the drive is a different type to that installed when
parameters were last saved on the drive. The reason for the trip can be identified by the sub-trip number.
Recommended actions:
•
Turn off the power, ensure the correct option modules are installed in the correct option slots and re-apply the power.
•
Confirm that the currently installed option module is correct, ensure option module parameters are set correctly and
perform a user save in Pr
mm.000.
SlotX Error
Option module in option slot X has detected a fault
202
207
212
The
SlotX Error
trip indicates that the option module in option slot X on the drive has detected an error. The reason for the
error can be identified by the sub-trip number.
Recommended actions:
•
See relevant
Option Module User Guide
for details of the trip
Trip
Diagnosis
Sub-trip
Reason
1
The module category cannot be identified
2
All the required customized menu table information has not been supplied or the tables supplied are corrupt
3
There is insufficient memory available to allocate the comms buffers for this module
4
The module has not indicated that it is running correctly during drive power-up
5
Module has been removed after power-up or it has stopped working
6
The module has not indicated that it has stopped accessing drive parameters during a drive mode change
7
The module has failed to acknowledge that a request has been made to reset the drive processor
8
The drive failed to correctly read the menu table from the module during drive power up
9
The drive failed to upload menu tables from the module and timed out (5 s)
Sub-trip
Reason
1
No module was installed previously
2
A module with the same identifier is installed, but the set-up menu for this option slot has been
changed, and so default parameters have been loaded for this menu.
3
A module with the same identifier is installed, but the applications menu for this option slot has been
changed, and so default parameters have been loaded for this menu.
4
A module with the same identifier is installed, but the set-up and applications menu for this option slot
have been changed, and so default parameters have been loaded for these menus.
>99
Shows the identifier of the module previously installed.