Fault code
F 3612
Fault message
Defective switching of output SBC2 (dynamic test)
Cause
Output switch status defective
Remedial action
Switch the device on/off
Fault code
F 3614
Fault message
Defective testing of upper limit of power supply (dynamic test)
Cause
Power supply defective
Remedial action
Check the power supply
Fault code
F 3616
Fault message
Defective testing of lower limit of power supply (dynamic test)
Cause
Power supply defective
Remedial action
Check the power supply
Fault code
F 3617
Fault message
Defective testing of STO output (static test)
Cause
Output switch status defective
Remedial action
Switch the device on/off
Fault code
F 3618
Fault message
Defective switching of output SBC1 (static test)
Cause
Output switch status defective
Remedial action
Switch the device on/off
Fault code
F 3619
Fault message
Internal fault – please contact the manufacturer
Fault code
F 3620
Fault message
Defective switching of output SBC2 (static test)
Cause
Output switch status defective
Remedial action
Switch the device on/off
Fault code
F 3621
Fault message
Internal fault – please contact the manufacturer
Fault code
F 3622
Fault message
Internal fault – please contact the manufacturer