Figure 7-1 Configuring the data format
The user may define all aspects of the data including speed, position and logic data,
plus switching conditions of logic elements on the terminal interface. Processed data is
subsequently displayed in registers in menu 20 on the drive.
The processed data is displayed in the row below and is limited to a total of 64 bits with
the current position of axis 1 appearing in Pr
20.021
. If the current speed of axis 1 is
also required, this value is displayed in Pr
20.022
.
Communication with the drive is performed automatically after the data cable is
connected to the unit. The peripheral devices are activated through Baud rate and serial
addresses in the
CTSafePro
with the data being sent in cyclic format.
The following drive parameters must be set to their default parameters for
communication to occur between the drive and the SI-Safety module.
•
Pr
11.023
= 1
•
Pr
11.024
= rtu
•
Pr
11.025
= 19200
NOTE