48
SI-Safety Installation & Operating Manual
Issue Number: 1
6
Start-up
6.1
Procedure
Start-up / commissioning must only be performed by suitably trained and skilled
personnel. Observe all safety instructions during start-up / commissioning.
6.1.1
LED display
Following a reboot, the following sequences run whenever a session is completed
without faults being reported. The result is displayed on the front panel LED display.
Table 6-1 Key to LED display
6.2
Configuration
Configuration is performed using the '
CTSafePro
' program. To be able to transmit data
to the module, a programming adapter is required, and its drivers need to be installed
before it is used for the first time.
CTSafePro
is a graphical PC tool which enables the configuration of the speed encoder
interface, definition of the safe motion functionality and logic operations. It also provides
testing and advanced diagnostic tools.
The configuration is saved and protected against line power failure within the module.
Refer to
CTSafePro help
for details of how to configure the SI-Safety module.
6.2.1
Downloading the configuration to the SI-Safety module
The configuration is downloaded to the SI-Safety module via a serial cable connected
between the PC and the SI-Safety module RJ45 port. Refer to
CTSafePro help
for
details of downloading the configuration.
Mode
Description
LED display
Start-up
Synchronization between the
two processor systems and
checking of the configuration
and firmware data
Off
RUN
Normal operation of the system.
All outputs are switched to
reflect the prevailing status of
the logic unit.
Flashing green (1 Hz)
STOP
In Stop mode, parameter and
program data can be loaded
externally.
Flashing red/green (1 Hz)
ALARM
Alarm can be reset by digital
input.
Flashing red /yellow (1 Hz)
Fault
Fault can only be reset by
power cycling.
Continuous red
Not validated
System running but not
validated
Flashing yellow (1 Hz)
An isolated serial communications cable must be used to connect the SI-Safety module
to IT equipment (i.e. laptop computers). Suitable cables are available from Control
Techniques.
WARNING
Summary of Contents for unidrive m