SI-Safety error types
9.1
SI-Safety error types
SI-Safety makes a distinction between two types of error as shown in Table 9-1.
Table 9-1 Distinction between fault types
Detection of errors in System A and System B:
•
System A: odd numbers
•
System B: even numbers
Type of error
Description
Impact on
system
Reset condition
Fault
Serious exception error caused by
program running in SI-Safety. Cyclical
program runtime no longer possible due
to technical safety reasons.
Display by system A. System B is in Stop
mode.
All outputs are
switched off.
Can be reset by
switching
SI-Safety on/off.
Alarm
Functional error caused by an external
process. Both systems continue running
in a cyclic manner to service all
requirements of the communication
interfaces. Scanning of the external
process is also maintained.
All outputs are
switched off.
Reset by
configurable input
Encoder
supervision
(ECS) alarm
When using the ECS function, outputs
are not switched off when an encoder
alarm is triggered.
ECS function
block delivers ‘1’
as a result
Reset by
configurable input