Alarm code
A 5001 / A 5002
Alarm message
Internal fault – please contact the manufacturer
Alarm code
A 5003 / A 5004
Alarm message
Fault at grouped input SMF1
Cause
Plausibility check for the grouped input has malfunctioned
Remedial action
Check configuration of digital input in accordance with project
planning and circuit diagram
Check the wiring
Alarm code
A 5005 / A 5006
Alarm message
Fault at grouped input SMF2
Cause
Plausibility check for the grouped input has malfunctioned
Remedial action
Check configuration of digital input in accordance with project
planning and circuit diagram
Check the wiring
Alarm code
A 5007 / A 5008
Alarm message
Fault at grouped input SMF3
Cause
Plausibility check for the grouped input has malfunctioned
Remedial action
Check configuration of digital input in accordance with project
planning and circuit diagram
Check the wiring
Alarm code
A 5009 / A 5010
Alarm message
Fault at grouped input SMF4
Cause
Plausibility check for the grouped input has malfunctioned
Remedial action
Check configuration of digital input in accordance with project
planning and circuit diagram
Check the wiring
Alarm code
A 5011 / A 5012
Alarm message
Internal fault – please contact the manufacturer
Alarm code
A 5013
Alarm message
Plausibility fault at individual input SMF11
Cause
Plausibility check for the individual input has malfunctioned
Remedial action
Check configuration of digital input in accordance with project
planning and circuit diagram
Check the wiring