RXi2-BP Hardware Reference Manual
Section 3
GFK-3187B
November 2020
Mounting
9
3.2
Panel Mounting
To mount the IPC in a panel mount configuration, the user will need to connect Mounting Panel
#R2B00ACCMP01 to the rear of the IPC:
1.
Place the mounting plate on the rear of the IPC.
2.
Using a T9 Torx driver, secure the mounting plate with the two provided M3x6 screws,
tightening to 0.6 Nm. (Do not overtighten.)
3.
For regular mounting, secure the mounting plate and IPC through the top and bottom
center holes. For more rugged applications, secure the mounting plate with the four
provided M3x6 screws in all four corners of the mounting panel.
Figure 4: Attaching Mounting Plate RXi2-BP IPC
Figure 5: RXi2-BP IPC DIN Rail pre-mounting