1
Introduction
The pressure transmitter measures and monitors pressure in a facility.
1.1
Pressure specifications
To ensure product performance and safety, adhere to the following specifications.
1.1.1
Measuring range
This table shows the range at which the pressure transmitter is able to measure pressure.
Pressure range
Measuring range limits
inH
2
O
mbar
1A
-2.0 to 40
-5 to 99.5
2A
-5.0 to 100
-12.4 to 248.8
psi
bar
3A
-14.5 to 14.5
-1 to 1
2B
-0.73 to 14.5
-0.05 to 1
4A
-1.45 to 20
-0.1 to 1.38
5A
-1.8 to 36
-0.124 to 2.48
6A
-14.5 to 55
-1 to 3.79
7A
-14.5 to 85
-1 to 5.86
8A
-14.5 to 145
-1 to 10
9A
-14.5 to 230
-1 to 15.9
1B
-14.5 to 360
-1 to 24.8
Note
The pressure transmitter is vacuum resistant. There are restrictions for nominal pressure
ranges at or below 4.35 psi (300 mbar). Adhere to the specifications in the data sheet.
1.1.2
Overpressure limits
The table in this topic shows maximum allowable pressure for the pressure transmitter.
CAUTION
Take appropriate measures to avoid exceeding the specified overpressure limits.
Quick Start Guide
Introduction
00825-0100-4327
January 2019
Quick Start Guide
5
Summary of Contents for Rosemount 326P
Page 1: ...Quick Start Guide 00825 0100 4327 Rev 01 January 2019 Rosemount 326P Pressure Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4327 4 Quick Start Guide ...
Page 14: ...Installation Quick Start Guide January 2019 00825 0100 4327 14 Quick Start Guide ...
Page 40: ...Setting ranges Quick Start Guide January 2019 00825 0100 4327 40 Quick Start Guide ...
Page 44: ...Product certifications Quick Start Guide January 2019 00825 0100 4327 44 Quick Start Guide ...
Page 47: ...Quick Start Guide 00825 0100 4327 January 2019 Quick Start Guide 47 ...