Hnc
: hysteresis function/NC
•
Fno
: window function/NO
•
Fnc
: window function/NC
•
I
: current signal proportional to pressure 4-20 mA
•
InEG
: current signal proportional to pressure 20-4 mA
8. Press
Mode/Enter
.
Set switching limits
Follow these steps to set the limits that cause the outputs to switch.
Procedure
1. Select
SP1
or
SP2
from the menu.
2. Press and hold
Set
to modify the parameter value.
3. Set the limit at which the output switches.
4. Press
Mode/Enter
.
5. Select
rP1
or
rP2
from the menu.
6. Press and hold
Set
to modify the parameter value.
7. Set the limit at which the output resets.
The rPx value is always lower than SPx. The pressure transmitter accepts only values
lower than the value for SPx.
8. Press
Mode/Enter
.
Automatically scale the analog output
Follow these steps to set the start and end value of the analog output to the current
system pressure reading. If the automatic setting is invalid, the pressure transmitter
displays UL or OL. After acknowledging an incorrect value, the pressure senor displays Err
and does not accept the incorrect value.
Procedure
1. Set the minimum pressure requested in the system.
a) Select
tASP
from the menu.
b) Press and hold
Set
.
The display flashes the current set value.
c) Release
Set
when the value stops flashing.
The pressure transmitter displays the new value.
d) Press
Mode/Enter
.
The current system pressure is defined as the start value for the analog
signal.
2. Set the maximum pressure requested in the system.
a) Select
tAEP
from the menu.
Quick Start Guide
Operation
00825-0100-4327
January 2019
Quick Start Guide
25
Summary of Contents for Rosemount 326P
Page 1: ...Quick Start Guide 00825 0100 4327 Rev 01 January 2019 Rosemount 326P Pressure Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4327 4 Quick Start Guide ...
Page 14: ...Installation Quick Start Guide January 2019 00825 0100 4327 14 Quick Start Guide ...
Page 40: ...Setting ranges Quick Start Guide January 2019 00825 0100 4327 40 Quick Start Guide ...
Page 44: ...Product certifications Quick Start Guide January 2019 00825 0100 4327 44 Quick Start Guide ...
Page 47: ...Quick Start Guide 00825 0100 4327 January 2019 Quick Start Guide 47 ...