Perform an automatic zero trim
Follow these steps to automatically scale the pressure offset by +/-5 percent. Use this after
installation to trim out any measurement offsets because of mounting effects.
Prerequisites
Ensure no pressure is applied to the pressure transmitter.
Procedure
1. Select
tCOF
from the menu.
2. Press and hold
Set
.
The current offset value appears then the current system pressure appears.
3. Release
Set
.
4. Press
Mode/Enter
to confirm the new offset value.
Setting output reaction to fault conditions
Follow these steps to modify how the outputs react to fault conditions.
Procedure
1. Select
FOU1
from the extended functions menu.
2. Press and hold
Set
to modify the parameter value.
3. Set the value for output 1.
•
On
: output 1 switches on in case of a fault.
•
OFF
: output 1 switches off in case of a fault.
•
OU
: output 1 switches irrespective of a fault as defined by parameters SP1, rP1
und OU1.
4. Select
FOU2
from the extended functions menu.
5. Press and hold
Set
to modify the parameter value.
6. Set the value for output 2.
•
On
: output 2 switches on in case of a fault, the analog signal goes to the upper
final value.
•
OFF
: output 2 switches off in case of a fault, the analog signal goes to the lower
final value.
•
OU
: output 2 switches irrespective of the fault as defined by parameters SP2,
rP2, OU2. The analog signal corresponds to the measured value.
Postrequisites
For more information on error messages, see
.
Quick Start Guide
Operation
00825-0100-4327
January 2019
Quick Start Guide
27
Summary of Contents for Rosemount 326P
Page 1: ...Quick Start Guide 00825 0100 4327 Rev 01 January 2019 Rosemount 326P Pressure Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4327 4 Quick Start Guide ...
Page 14: ...Installation Quick Start Guide January 2019 00825 0100 4327 14 Quick Start Guide ...
Page 40: ...Setting ranges Quick Start Guide January 2019 00825 0100 4327 40 Quick Start Guide ...
Page 44: ...Product certifications Quick Start Guide January 2019 00825 0100 4327 44 Quick Start Guide ...
Page 47: ...Quick Start Guide 00825 0100 4327 January 2019 Quick Start Guide 47 ...