Set simulation duration
Follow these steps to set the duration of the simulation. Simulations can run between 1-60
minutes.
Procedure
1. Select
S.TIM
from the simulation menu.
2. Press and hold
Set
to modify the parameter value.
3. Set the duration value between 1-60 minutes.
4. Press
Mode/Enter
.
Start a simulation
Follow these steps to start a simulation.
Prerequisites
Set the simulation parameters.
Procedure
1. Select
S.ON
from the simulation menu.
2. Press and hold
Set
until the pressure transmitter displays
SIM
and the current
operating indicator.
Current operation indications include:
•
Current system pressure if
SEL
=
OU
.
•
Simulated measured value set in
S.Pr
if
SEL
=
Proc
.
The simulation runs until the set duration time elapses. Then, the pressure transmitter
displays
S.OFF
then
SEL
.
Abort a simulation
Follow these steps to stop a simulation before the duration time elapses.
Procedure
Press
Mode/Enter
or
Set
.
The pressure transmitter displays
S.OFF
for two seconds then displays
SEL
.
Operation
Quick Start Guide
January 2019
00825-0100-4327
32
Quick Start Guide
Summary of Contents for Rosemount 326P
Page 1: ...Quick Start Guide 00825 0100 4327 Rev 01 January 2019 Rosemount 326P Pressure Transmitter ...
Page 2: ...2 ...
Page 4: ...Contents Quick Start Guide January 2019 00825 0100 4327 4 Quick Start Guide ...
Page 14: ...Installation Quick Start Guide January 2019 00825 0100 4327 14 Quick Start Guide ...
Page 40: ...Setting ranges Quick Start Guide January 2019 00825 0100 4327 40 Quick Start Guide ...
Page 44: ...Product certifications Quick Start Guide January 2019 00825 0100 4327 44 Quick Start Guide ...
Page 47: ...Quick Start Guide 00825 0100 4327 January 2019 Quick Start Guide 47 ...