Liebert iCOM Control—Firmware Version XP1.00.010.STD
48
Figure 50 Diagnostics/Service Mode screen, page 3 of 6
Page 3 applies to the Liebert XDC only. No Liebert XDP parameters are present.
Figure 51 Diagnostics/Service Mode screen, page 4 of 6
Manual Mode Control Type
—Not currently used.
Manual Deviation
—Not currently used.
Analog Output Ramp 1
—Sets the value of Analog Output 1 value as a percentage. The factory
default for the Liebert XDP is the Valve % Open.
Analog Output Ramp 2
—Sets the value of Analog Output 2 value as a percentage. The factory
default for the Liebert XDP is the Call for Cooling.
Analog Output Ramp 3
—Sets the value of Analog Output 3 value as a percentage. The factory
default for the Liebert XDP is the CW Temp.
Analog Output Ramp 4
—Sets the value of Analog Output 4 value as a percentage. The factory
default for the Liebert XDP is the refrigerant temperature.
Alarm Relay
—Used to activate the Liebert iCOM’s common alarm relay output.
Warning Relay
—Used to activate the Liebert iCOM’s warning relay output.
DIAGNOSTICS/SERVICE MODE (page 3 of 6)
UNIT 01
S323
S324
S325
S326
S327
S328
S329
S330
S331
S332
S333
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
????
DIAGNOSTICS/SERVICE MODE (page 4 of 6)
UNIT 01
S334
S335
S336
S337
S338
S339
S340
S341
S342
S343
S344
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
????
Manual Mode Control Type
Full
Manual Deviation
12%
Analog Output Ramp 1
30%
Analog Output Ramp 2
0%
Analog Output Ramp 3
60%
Analog Output Ramp 4
58%
Alarm Relay
Off
Warning Relay
Off
Summary of Contents for Liebert XDP
Page 2: ......