Liebert iCOM Control—Firmware Version XP1.00.010.STD
52
Figure 56 Set Alarms screen, page 3 of 7
HIGH TEMP SENSOR A
—Enables or disables the High Temperature Sensor A event, which occurs
when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOW TEMP SENSOR A
—Enables or disables the Low Temperature Sensor A event, which occurs when
the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
HIGH TEMP SENSOR B
—Enables or disables the High Temperature Sensor B event, which occurs
when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is
reported as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
LOW TEMP SENSOR B
—Enables or disables the Low Temperature Sensor B event, which occurs
when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is
reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting
the event.
HIGH DEWPOINT
—Enables or disables the High Dewpoint event, which occurs when the
calculated dew point at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
SENSOR A FAILURE
—Enables or disables the Sensor A Failure event, which occurs when the
control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
SENSOR B FAILURE
—Enables or disables the Sensor B Failure event, which occurs when the
control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a
warning or a message. Specifies how long the control waits before reporting the event.
HIGH CHILLED WATER TEMP
—Enables or disables the High Chilled Water Temp event, which
occurs when the reading from Supply Chilled Water Sensor is above the user-specified alarm setpoint.
Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control
waits before reporting the event.
SUPPLY CW SENSOR FAILURE
—Enables or disables the Supply CW Sensor Failure Failure
event, which occurs when the control no longer senses a signal from Supply CW Sensor. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
SET ALARMS (page 3 of 7)
UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
HIGH TEMP SENSOR A
LOW TEMP SENSOR A
HIGH TEMP SENSOR B
LOW TEMP SENSOR B
HIGH DEWPOINT
SENSOR A FAILURE
SENSOR B FAILURE
HIGH CHILLED WATER TEMP
SUPPLY CW SENSOR FAILURE
S223
S224
S225
S226
S227
S228
S229
S230
S231
S232
S233
S234
S235
DELAY
30
30
30
30
30
30
????
TYPE
ALM
ALM
ALM
ALM
ALM
ALM
ALM
ALM
ALM
EN-DIS
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE