Liebert iCOM Control—Firmware Version XP1.00.010.STD
50
Figure 54 Set Alarms screen, page 1 of 7
High Room Air Temperature
—Sets the threshold for a high room air temperature alarm. The
range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F
(26.7°C).
Low Room Air Temperature
—Sets the threshold for a low room air temperature alarm. The range
for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).
High Room Dewpoint
—Sets the threshold for a return high dew point alarm. The range for the
high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).
High Refrigerant Temperature
—Sets the threshold for a high a refrigerant temperature alarm.
The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the
default is 80°F (26.7°C).
High Chilled Water Temperature
—Sets the threshold chilled water temperature for a supply high
chilled water temperature alarm. The range for the high supply refrigerant temperature alarm is
from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).
SET ALARMS (page 1 of 7)
UNIT 01
S201
S202
S203
S204
S205
S206
S207
S208
S209
S210
S211
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
????
High Room Air Temperature
88.0°F
Low Room Air Temperature
55.0°F
High Room Dewpoint
65.0°F
High Refrigerant Temperature
80.0°F
High Chilled Water Temperature
60.0°F