Liebert iCOM Control—Firmware Version XP1.00.010.STD
37
Figure 34 Sensor Data screen, page 2 of 2
Daily High Temperature
—Shows the highest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Daily Low Temperature
—Shows the lowest temperature in a rolling 24 hour period for either
remote Sensor A or remote Sensor B.
Daily High Humidity
—Shows the highest humidity in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Humidity
—Shows the lowest humidity in a rolling 24 period for either remote Sensor A
or remote Sensor B.
Daily High Dew Point
—Shows the highest dew point in a rolling 24 hour period for either remote
Sensor A or remote Sensor B.
Daily Low Dew Point
—Shows the lowest dew point in a 24 hour period for either remote Sensor A
or remote Sensor B.
Daily High Refrigerant Temperature
—Shows the highest supply refrigerant temperature in a
rolling 24 hour period from the Liebert XDP to the modules.
Daily Low Refrigerant Temperature
—Shows the lowest supply refrigerant temperature in a
rolling 24 hour period from the Liebert XDP to the modules.
Daily High Chilled Water Temperature
—Shows the highest chilled water supply temperature
being delivered to the Liebert XDP in a rolling 24 hour period.
Daily Low Chilled Water Temperature
—Shows the lowest chilled water return temperature
being delivered to the Liebert XDP in a rolling 24 hour period.
SENSOR DATA (page 2 of 2)
UNIT 01
U313
U314
U315
U316
U317
U318
U319
U320
U321
U322
U323
U324
This window is READ ONLY
Daily High Temperature
07:49:57
72°F
Daily Low Temperature
07:11:30
64°F
Daily High Humidity
11:31:46
45%
Daily Low Humidity
07:56:18
34%
Daily High Dew Point
07:47:26
45°F
Daily Low Dew Point
08:02:20
37°F
Daily High Refrigerant Temp
13:01:25
69°F
Daily Low Refrigerant Temp
13:01:11
69°F
Daily High CW Temp
14:01:33
55°F
Daily Low CW Temp
14:01:45
55°F