Liebert iCOM Control—Firmware Version XP1.00.010.STD
63
This screen selects the operation of an active alarm for each smart module. Each event can be enabled
or disabled and can be set to operate as an alarm, a warning or a message. The delay is the time the
control waits before reporting the event.
Alarm
: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display.
Warning
: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer/front display and flashes the red LED on the display.
Message
: Shows the event in the event viewer and on the front display.
Fan Control Type
—Sets the fan control mode. Values can be OFF, ON, ON ALL and TEMP CNTL.
Disable Local Button
—Disables the push button on the front of the smart module. To disable the
push button, set the parameter to YES. To re-enable the push button, set the parameter to NO.
Flash LED at Module
—Flashes the LED on the smart module when set to Yes.
Set Module Label
—A four-character label consisting of two letters and two numerals. This is the
standard nomenclature for Data Center Grid assignment of racks. Additionally, the module’s location
can be denoted with 10 characters, either letters or non-alphanumeric characters from a built-in list.
Either or both labels can be used and are entered using this screen.
Supply Air Temp Limit
—Sets the high and low supply air temperature to from the module. An
alarm will occur if the temperature falls outside the limits.
Return Air Temp Limit
—Sets the high and low return air temperature to from the module. An
alarm will occur if the temperature falls outside the limits.
Firmware Version
—Displays the firmware version installed on the smart module.
Figure 70 Module Setup screen, page 1 of 20
MODULE SETUP (page 1 of 20)
UNIT 01
PASSWORD (Actual Level 0)
NODE ID 81
CONDENSATION DETECTED
LOCAL MODULE SHUTDOWN
SENSOR FAILURE
FAN FAILURE
FAN CONTROL MODE
DISABLE LOCAL BUTTON
FLASH LED AT MODULE
SET MODULE LABEL
SUPPLY AIR TEMP LIMITS
RETURN AIR TEMP LIMITS
FIRMWARE VERSION
S901
S902
S903
S904
S905
S906
S907
S908
S909
S910
S911
S912
S913
DELAY
15
15
30
30
????
TYPE
ALM
ALM
ALM
EN-DIS
ENABLE
ENABLE
ENABLE
ENABLE
A Z 81
High 80 Low 50 °F
High 120 Low 60 °F
XXX.XX.XXX
OFF
NO
NO