Liebert iCOM Control—Firmware Version XP1.00.010.STD
54
Figure 58 Set Alarms screens, pages 5 and 6
Pages 5 and 6 apply to the Liebert XDC only. No Liebert XDP parameters are present.
Figure 59 Set Alarms screen, page 7 of 7
CONDENSATION DETECTED
—Enables or disables the Condensation Detected event, which
occurs when water is detected at a Liebert XD cooling module. Sets how the event is reported: as an
alarm, a warning or a message. Specifies how long the control waits before reporting the event.
FAN FAILURE
—Enables or disables the Fan Failure event, which occurs when a fan failure occurs
at a Liebert XD cooling module. Sets how the event is reported: as an alarm, a warning or a message.
Specifies how long the control waits before reporting the event.
CUSTOMER INPUT 1
—Enables or disables the Customer Input 1 event, which occurs when 24VAC
is applied to the input. Sets how the event is reported: as an alarm, a warning or a message. Specifies
how long the control waits before reporting the event.
SMOKE DETECTED
—Enables or disables the Smoke Detected event, which occurs when the
Customer Input 1 is configured for “Smoke Detected” and 24VAC is applied to the input. Sets how the
event is reported: as an alarm, a warning or a message. Specifies how long the control waits before
reporting the event.
NOTE
This is not a room smoke detector and is not intended to replace external smoke detectors.
SET ALARMS (page 5 of 7)
UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
S259
S250
S251
S252
S253
S254
S255
S256
S257
S258
S259
S260
S261
DELAY
????
TYPE
EN-DIS
SET ALARMS (page 6 of 7)
UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
S262
S263
S264
S265
S266
S267
S268
S269
S270
S271
S272
S273
S274
DELAY
????
TYPE
EN-DIS
SET ALARMS (page 7 of 7)
UNIT 01
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0)
CONDENSATION DETECTED
FAN FAILURE
CUSTOMER INPUT 1
SMOKE DETECTED
WATER UNDER FLOOR
UNIT X DISCONNECTED
WORKING HRS EXCEEDED
CALL SERVICE
LOSS OF POWER
S275
S276
S277
S278
S279
S280
S281
S282
S283
S284
S285
S286
S287
DELAY
3
3
5
5
5
5
????
TYPE
ALM
ALM
ALM
ALM
ALM
WRN
WRN
ALM
WRN
EN-DIS
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE
ENABLE