![Emerson Fisher FIELDVUE DVC6000 HW2 Instruction Manual Download Page 70](http://html.mh-extra.com/html/emerson/fisher-fieldvue-dvc6000-hw2/fisher-fieldvue-dvc6000-hw2_instruction-manual_102336070.webp)
Instruction Manual
D103785X012
Maintenance and Troubleshooting
June 2017
70
5. Set the DIP switch on the PWB assembly according to table 6‐2. On units that have the optional 4-20 mA position
Table 6‐2. DIP Switch Configuration
Switch Label
Operational Mode
DIP Switch Position
PT-PT
420 mA PointtoPoint Loop
LEFT
Multi
24 VDC MultiDrop Loop
RIGHT
1. Refer to figure 6‐5 for switch location.
Table 6‐3. Output Switch Configuration
Switch Label/Function
DIP Switch Position
Transmitter
LEFT
Switch
RIGHT
1. Refer to figure 6‐5 for switch location.
X0432
Figure 6‐5. Printed Wiring Board (PWB) Connections and Settings
TRANSMITTER/SWITCH
SELECTION
TRAVEL SENSOR
CONNECTOR
TERMINAL BOX
CONNECTOR
OPERATIONAL
MODE SELECTION
TRAVEL SENSOR
CONNECTOR
TERMINAL BOX
CONNECTOR
OPERATIONAL
MODE SELECTION
X0463
Note
For the digital valve controller to operate with a 4 to 20 mA control signal, be sure the DIP switch is in the point‐to‐point loop
position.
6. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.
7. Setup and calibrate the DVC6005 HW2 base unit.