Instruction Manual
D103785X012
Configuration
June 2017
40
Change to HART 5 / Change to HART 7
Field Communicator
Service Tool > Maintenance > Change to HART 5 / Change to HART 7 (3-5-3) HC or
(3-5-4) AD, PD or
(3-5-5) ODV
Note
This procedure must never be done while the valve is in service and controlling the process. Depending on the control system or
asset management system attached, complete system reset may be required to reestablish HART communication. Consult the
system documentation for further information.
This procedure changes the instrument from HART Universal Revision 5 to HART Universal Revision 7 (or vice versa).
Before proceeding, verify that your systems are prepared to support HART Universal Revision 7 devices. Follow the
prompts on the Field Communicator display.