Instruction Manual
D103785X012
Configuration
June 2017
19
Section 3 Configuration
Guided Setup
Field Communicator
Configure > Guided Setup (2‐1)
The following procedures will guide you through the instrument setup process.
D
Device Setup
—
This procedure is used to configure actuator and valve information, calibrate the valve assembly, and
assign the tuning set for the valve assembly.
D
Performance Tuner (instrument level AD, PD, ODV)
—
This procedure executes a simple step response test and then
D
Stabilize Optimize (instrument level HC)
—This procedure permits you to adjust valve response by changing the
digital valve controller tuning. See page 30 for additional information.
Manual Setup
33
Manual Setup
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Table 3‐1. Default Detailed Setup Parameters
Setup Parameter
Default Setting
Instrument
Configuration
Control Mode
Analog
Restart Control Mode
Resume Last
Analog In Range Low
4 mA
Analog In Range High
20 mA
Analog Input Units
mA
Local AutoCal Button
Disabled
Polling Address
0
Burst Mode Enable
No
Burst Command
3
Cmd 3 (Trending) Pressure
A-B
Dynamic Response and
Tuning
Input Characterization
Linear
Travel Limit High
125%
Travel Limit Low
-25%
Travel/Pressure Cutoff High
99.46%
Travel/Pressure Cutoff Low
0.50%
Set Point Rate Open
0%/sec
Set Point Rate Close
0%/sec
Set Point Filter Time (Lag Time)
0 sec
Integrator Enable
Yes
Integral Gain
9.4 repeats/minute
Integral Deadzone
0.26%
-continued on next page-