Instruction Manual
D200156X012
4194HA, HB, HC Controllers
July 2018
29
13. Adjust the proportional band to 100 percent direct action.
14. Apply differential pressure to the differential pressure unit or, if link 1 was disconnected, remove the tape from the
process indicator and move the indicator until it aligns with the right‐hand edge of the set point indicator (as shown
in figure 4‐1).
Controller output should be within 0.14 bar (2 psig) of the supply pressure.
15. Apply differential pressure to the differential pressure unit or, if disconnected, move the process indicator to the
left‐hand edge of the set point indicator (as shown in figure 4‐1).
Figure 4‐1. Alignment of the Process Pointer with the Set Point Adjustment
RIGHT‐HAND EDGE
LEFT‐HAND EDGE
W4039
W4038
Controller output pressure should go to 0 psig.
16. Adjust the proportional band to 100 percent reverse action.
17. Pressure the differential pressure unit or, if disconnected, move the process indicator to align with the right‐hand
edge of the set point indicator. The controller output should be 0 psig.
18. Pressure the differential pressure unit or, if disconnected, position the process indicator to align with the left‐hand
edge of the set point indicator. The controller output should be within 0.14 bar (2 psig) of supply pressure.
20. Set the proportional band to 400 percent in the desired controller action. Replace the proportional band indicator
cover (key 36) and install the two machine screws (key 6). If link 1 was disconnected, reconnect link 1 to the drive
arm using the same hole connections.
21. If the controller has the external feedback option, disconnect the outside tubing which connects the external
feedback connection to the output connection.
22. For 4194HB and HC controllers with the anti‐reset windup option (suffix letter F), remove the two machine screws
(key 53), valve cover (key 51), and two O‐rings (key 52) installed in step 1 of this procedure. Install the differential
relief valve (key 55).