4194HA, HB, HC Controllers
July 2018
65
Flapper leveling screw numbers and adjustments are shown in figure 3‐1. Provide a means of applying supply pressure
to the controller and plug the output connection. After performing the flapper alignment procedure, go to the
appropriate startup procedure.
4194HA Proportional‐Only Controllers
1. For controllers with manual set point, move the set point adjustment to 50 percent of the process scale range. For
controllers with remote set point (suffix letter M), adjust the remote set point pressure until the set point indicator
is at 50 percent of the process scale range.
2. Apply differential pressure equal to 50 percent of the process scale range. An alternate method is to disconnect link
1 from the drive arm then manually position the process indicator at 50 percent of the process scale range. Tape the
process indicator in place.
3. Remove the screws (key 6) and lift off the proportional band indicator cover (key 36).
4. Adjust the proportional band indicator to between DIRECT and REVERSE.
5. The output of the controller should be:
D
0.62
±
0.007 bar (9
±
0.1 psig) for a 0.2 to 1.0 bar (3 to 15 psig) output
D
1.2
±
0.01 bar (18
±
0.2 psig) for a 0.4 to 2.0 bar (6 to 30 psig) output
To adjust controller output, adjust flapper leveling screw 2 (figure 3‐1).
6. Adjust the proportional band to 20 percent DIRECT. The output of the controller should remain essentially the
same.
D
0.62
±
0.017 bar (9
±
0.25 psig) for a 0.2 to 1.0 bar (3 to 15 psig) output
D
1.2
±
0.03 bar (18
±
0.5 psig) for a 0.4 to 2.0 bar (6 to 30 psig) output
7. Adjust the proportional band to 20 percent REVERSE. The output of the controller should remain essentially the
same.
D
0.62
±
0.017 bar (9
±
0.25 psig) for a 0.2 to 1.0 bar (3 to 15 psig) output
D
1.2
±
0.03 bar (18
±
0.5 psig) for a 0.4 to 2.0 bar (6 to 30 psig) output
leveling screws.
9. Release the process indicator and connect link 1 to the drive arm.
10. Set the proportional band adjustment to 400 percent in the desired controller action (DIRECT or REVERSE). Replace
the proportional band cover.
4194HB Proportional‐Plus‐Reset and 4194HC Proportional‐Plus‐Reset‐Plus‐ Rate Controllers
Note
4194HB and HC controllers with the anti‐reset windup option (suffix letter F) are supplied with two O‐rings (key 52, figure
6‐1/CONTROLLER COMMON PARTS), valve cover (key 51, figure 6‐1/VIEW E, 4194HB CONTROLLERS or VIEW E, 4194HC
CONTROLLERS), and two machine screws (key 53, figure 6‐1/VIEW E, 4194HB CONTROLLERS or VIEW E, 4194HC CONTROLLERS).
Use these parts in the next step.
1. For 4194HB and HC controllers with the anti‐reset windup option (suffix letter F), remove the differential relief valve
(key 55, figure 6‐1/VIEW E, 4194HB CONTROLLERS, OPTION F or VIEW E, 4194HC CONTROLLERS, OPTION F). Install
the two O‐rings (key 52) and valve cover (key 51) provided with the controller. Secure the valve cover over the two
O‐rings with the two machine screws (key 53) also provided.