This chapter introduces the basic procedures and parameter setting methods for the elevator door control system using
EV3200 series inverter. Applications of speed control and distance control are introduced below, including the system
configuration and parameter settings.
7.1 Motor Type Setup
Prior to motor tuning, first of all, you need to set the tuning parameters correctly according to the motor. Then, you can press
the
key to start tuning. During the tuning process, the keypad displays
. When the tuning is over, the parameters will
be saved automatically. Follow the procedures shown in Figure 7-1 to set the tuning parameters.
Motor type?
Start
Synchronous
Asynchronous
Set motor type
F6.00=1
Set PG pulse number
F4.01
Set control mode
F0.01=1
Set motor rated power
F6.01
Set motor rated voltage
F6.02
F6.03
F6.05
F6.06
F6.07=1
Start tunning
End
Set max output power
F0.04
Set control mode
F0.02=0
Set motor rated current
Set motor rated freq.
Set motor rated run speed
Set tunning parameters
Figure 7-1 Motor tuning procedures
Note
During the tuning, the motor should be connected without load. Otherwise, the motor parameters obtained from tuning will be incorrect,
and the tuning might fail.