User Manual
Appendix B
GFK-2849A
Oct 2019
Protocol Implementation Conformance Statements (PICS)
123
CPU320
Combined
I/O memory (Kbytes)
CPU Sweep
time
(msec)
I/O Loop back time
in msec with Polling
rate2 = 1000 msec
Avg (Min, Max)
I/O Loop back time
in msec with RCBs
enabled for inputs
Avg (Min, Max)
4
7.02
988 (499, 1033)
73 (42, 177)
8
11.9
985 (997,1114)
92 (48, 354)
16
22.5
984 (291, 1038)
161 (65, 562)
32
43.8
972 (261, 1051)
233 (85, 654)
1
RCBs = Report Control Blocks. The PPVs for loopback are part of RCB with trigger options set as
“TrgOp data
-chang
e” and other PPVs are configured for polling rate of 1000msec. This can be set in
the IEC 61850 Configurator.
2
The polling rate for each IED connection can be configured in IEC 61850 Configurator.