User Manual
Appendix E
GFK-2849A
Oct 2019
Protocol Implementation extra Information for Testing (PIXIT)
139
Description
Value / Clarification
Describe how to get the actual
setting group values
The current value of variables created for SG attributes are
directly mapped to the PLC Protocol Variable (PPV). Below is
one example of a PPV with SG attributes.
IEC 61850 Configurator
The IEC 61850 variable as seen in the Configurator dialogue:
Dev.IEDDevice.PTOV1/TmMult/setMag.f[SG]
PLC Protocol Variable(s)
The PPV set that gets created automatically in the RX3i
controller project for the above IEC 61850 variable:
S8_Dev_IEDDevice.PTOV1_TmMult.setMag_f_SG
Describe how the client
behaves in case of:
GetSGCBValues response-
The configured SG is
different than the actual
setting group
GetSGCBValues response- [ Invalid Bit
–
(Status bit INVALID of
variables mirroring DO/DA)]
The configured SG is different than the actual setting group -
SGCB is read out via MMS at each associate
E-8
Reporting Model PIXIT
Reporting Model PIXIT
Description
Value / Clarification
Does the client search for RCB in
all logical nodes?
Yes: all logical nodes are searched (for automatic allocation of
URCBs)
Does the client search for RCB
when the logical nodes are not
specified?
Yes: logical nodes are searched for static allocation of URCBs
and BRCBs. BRCBs are selectable online from Server only.
Which dynamic RCB attributes
are/can be configured by the
client
RptID
No
DataSet
No
Optional fields
Yes (fixed†)
Trigger conditions Yes (common for all RCBs)
Buffer time
No
Integrity period
No
†
These are pre-configured and cannot be changed
dynamically.
Does the client supports IEDs
with indexed and non-indexed
report control blocks (RCB)
Buffered RCB indexed
Yes
Buffered RCB not indexed
Yes
Unbuffered RCB indexed
Yes
Unbuffered RCB not indexed
Yes
The supported trigger
conditions are:
Integrity
Yes
data change
Yes