![Emerson ECM850 User Manual Download Page 142](http://html.mh-extra.com/html/emerson/ecm850/ecm850_user-manual_101596142.webp)
User Manual
Appendix E
GFK-2849A
Oct 2019
Protocol Implementation extra Information for Testing (PIXIT)
135
Description
Value / Clarification
Describe how to force a GetAllDataValues
request
Not Used
Describe how the client behaves in case of:
GetDataDefinition response
GetLogicalDeviceDirectory response
GetAllDataValues response
GetDataValues response
SetDataValues response-
GetDataDefinition response- [I-
Bit† ]
GetLogicalDeviceDirectory response- [I-
Bit† ]
GetAllDataValues response- [not supported ]
GetDataValues response- [I-
Bit† ]
SetDataValues response- [Error output in
WRITE and/or value in variable will not accept
change ]
† Status bit INVALID of
variables mirroring
DO/DA
E-5
Data Set Model PIXIT
Data Set Model PIXIT
Description
Value / Clarification
Describe how to force a GetDataSetValues
request.
Not Used
Describe how to force a SetDataSetValues
request.
Not Used
Describe how to force a DeleteDataSet request.
Not Used
Describe how the client handles following
dataset mismatches between the SCL and the
data sets exposed via MMS:
1.
new dataset element
2.
missing dataset element
3.
Reordered dataset members in a dataset
of a different data type.
4.
Reordered dataset members in a dataset
of the same data type.
The SCL file is not used in the Client module
during runtime communication. This file can
be used to preconfigure IEC 61850 variables
[offline configuration] in the RX3i controller
project using Machin
e Edition’s “IEC 61850
Configurator” dialogue.
Describe how the client behaves in case of:
—
GetLogicalNodeDirectory (DATA-SET)
response-
—
GetDataSetDirectory response-
Data will be polled (no reporting)
Does the client support the creation of:
—
persistent datasets
—
non-persistent datasets
No
No
Describe how the client behaves in case of:
—
CreateDataSet response-
—
DeleteDataSet response-
Not Used
Not Used