User manual IPM500 EN rel1.0.doc
iPro Series
39/48
ALARM
AWT3
Description
Thermal alarm for the pump 3
Activation Condition
Alarm condition on defined digital input by param EX18
System status
If there is a pump available, the system activates it. Otherwise the system stops.
ALARM
AGEN
Description
Security stop
Activation Condition
Alarm condition on defined digital input by param EX39
System status
The system stops
ALARM
AU01 – AU10
Description
Critical alarm from the Unit 1-10
Activation Condition
The alarm condition is provided by the slave unit and stored into the unit structure
System status
The unit is bypassed from the regulation. The system stays on and replace the unit with the backup unit if
available
ALARM
AN01 – AN10
Description
Notify alarm from the Unit 1- 10
Activation Condition
The notify condition is provided by the slave unit and stored into the unit structure
System status
The system only makes a notify about this alarm. No modifies on regulation
ALARM
AFL1
Description
Flow switch 1 alarm
Activation Condition
Alarm condition on defined digital input by param EX32
System status
The system performs the flow switch and pumps checks and then eventually stops
ALARM
AFL2
Description
Flow switch 2 alarm
Activation Condition
Alarm condition on defined digital input by param EX33
System status
The system performs the flow switch and pumps checks and then eventually stops
ALARM
AWP1
Description
Water pump alarm for the pump 1
Activation Condition
Water pump alarm after a flow switch alarm condition
System status
The system performs the flow switch and pumps checks and then eventually stops
Special NOTE
This alarm must be reset manually or the pump will be ignored in the regulation
ALARM
AWP2
Description
Water pump alarm for the pump 2
Activation Condition
Water pump alarm after a flow switch alarm condition
System status
The system performs the flow switch and pumps checks and then eventually stops
Special NOTE
This alarm must be reset manually or the pump will be ignored in the regulation
ALARM
AWP3
Description
Water pump alarm for the pump 3
Activation Condition
Water pump alarm after a flow switch alarm condition
System status
The system performs the flow switch and pumps checks and then eventually stops
Special NOTE
This alarm must be reset manually or the pump will be ignored in the regulation
ALARM
APRS
Description
Pressure switch alarm
Activation Condition
Alarm condition on defined digital input by param EX39
System status
The system stops
ALARM
ALOB
Description
Overboost time alarm
Activation Condition
After the timed overboost, the system cannot reach the set point
System status
ON with active alarm (the system continues to regulate).
Special NOTE
This alarm must be reset manually. The timer restarts once the alarm is reset.