User manual IPM500 EN rel1.0.doc
iPro Series
38/48
ALARM
ALCF9
Description
Check the congruence between the parameter EX38 and the parameter EX39
Activation Condition
EX01 = 1 AND (EX38=1 AND EX39=0)
System status
The master stay in OFF
ALARM
ALCF10
Description
Check the congruence between the parameters CF03 and CF04 and the parameter EX01
Activation Condition
((CF03=2 AND CF02<>1) OR (CF04=4 AND CF02<>0)) AND (EX01=0 OR EX07=0)
System status
The master stay in OFF
ALARM
ALCF11
Flag
ALARM_CONFIG_ANALOGUE_INPUTS
Description
Check the congruence between the parameters EX03 – EX07 and EX01 is enabled
Activation Condition
NOT (EX03 <> EX04 <> EX05 <> EX06 <> EX07) AND EX01
System status
The master stay in OFF
ALARM
ALCF12
Description
Check the congruence between the parameters EX03–EX07, EX14, EX16, EX18, EX28, EX32, EX33, EX34,
EX36, EX39 and the parameter EX01
Activation Condition
NOT (EX03<>EX04<>EX05<>EX06<>EX07<>EX14<>EX16<>EX18<>
EX28<>EX32<>EX33<>EX34<>EX36<>EX39) AND EX01
(It means the meaning of the configuration and not the value. In case of DI the probes start from 4)
System status
The master stay in OFF
ALARM
ALCF13
Description
Check the congruence between the parameters EX11 – EX013 and the parameter EX01
Activation Condition
NOT (EX11 <> EX12 <> EX13) AND EX01
System status
The master stay in OFF
ALARM
APEI
Description
Evaporator inlet probe alarm
Activation Condition
EX03 > 0 AND Probe alarm on selection
System status
The regulation uses the slave probes instead of the expansion probe
ALARM
APEO
Description
Evaporator outlet probe alarm
Activation Condition
EX04 > 0 AND Probe alarm on selection
System status
The regulation uses the slave probes instead of the expansion probe
ALARM
APCI
Description
Condenser inlet probe alarm
Activation Condition
EX05 > 0 AND Probe alarm on selection
System status
The regulation uses the slave probes instead of the expansion probe
ALARM
APCO
Description
Condenser outlet probe alarm
Activation Condition
EX06 > 0 AND Probe alarm on selection
System status
The regulation uses the slave probes instead of the expansion probe
ALARM
APCT
Description
Tank probe alarm
Activation Condition
EX07 > 0 AND Probe alarm on selection
System status
The regulation stops (No tank probes available on slaves)
ALARM
AWT1
Description
Thermal alarm for the pump 1
Activation Condition
Alarm condition on defined digital input by param EX14
System status
If there is a pump available, the system activates it. Otherwise the system stops.
ALARM
AWT2
Description
Thermal alarm for the pump 2
Activation Condition
Alarm condition on defined digital input by param EX16
System status
If there is a pump available, the system activates it. Otherwise the system stops.