User manual IPM500 EN rel1.0.doc
iPro Series
27/48
6.1.2
PARAMETERS ST
This group contain all those parameters used to setup the system thermoregulation.
Parameter
Description
Minimum
Value
Maximum
Value
UM
Resolution
SET POINT AND BAND SETTINGS
ST01
Cooling system set point
ST02
ST03
°C
°F
Dec
Int
ST02
Minimum value for cooling system set point
-50.0
-58
ST01
°C
°F
Dec
Int
ST03
Maximum value for cooling system set point
ST01
110.0
230
°C
°F
Dec
Int
ST04
Heating system set point
ST05
ST06
°C
°F
Dec
Int
ST05
Minimum value for heating system set point
-50.0
-58
ST04
°C
°F
Dec
Int
ST06
Maximum value for heating system set point
ST04
110.0
230
°C
°F
Dec
Int
ST07
Cooling system regulation band (in accord with the regulation
type defined by CF01 this parameter may assume different
meanings in case of proportional or neutral zone regulations)
0.1
0
25.0
45
°C
°F
Dec
Int
ST08
Heating system regulation band (in accord with the regulation
type defined by CF01 this parameter may assume different
meanings in case of proportional or neutral zone regulations)
0.1
0
25.0
45
°C
°F
Dec
Int
SPECIFIC PARAMETRS FOR NEUTRAL ZONE REGULATION
ST09
Delay for the forced insertion within the neutral band
0
250
Min
-
ST10
Delay for the forced resource rotation within the neutral band
0
999
Hur
-
ST11
Delay for the neutral band step insertion
0
250
Sec
-
ST12
Delay for the neutral band step removal
0
250
Sec
-