User manual IPM500 EN rel1.0.doc
iPro Series
29/48
3=digital output 3
4=digital output 4
5=digital output 5
6=digital output 6
EX12
Resource defined as water pump 2
0=disabled
1=digital output 1
2=digital output 2
3=digital output 3
4=digital output 4
5=digital output 5
6=digital output 6
0
6
-
-
EX13
Resource defined as water pump 3
0=disabled
1=digital output 1
2=digital output 2
3=digital output 3
4=digital output 4
5=digital output 5
6=digital output 6
0
6
-
-
EX14
Resource defined as water pump 1 thermal alarm
0=disabled
1=digital input 1
2=digital input 2
3=digital input 3
4=analog input 1 configured as digital input
5=analog input 2 configured as digital input
6=analog input 3 configured as digital input
7=analog input 4 configured as digital input
8=analog input 5 configured as digital input
9=analog input 6 configured as digital input
10=analog input 7 configured as digital input
0
10
-
-
EX15
Polarity for the resource defined as thermal alarm for water
pump 1
0=alarm active if the contact is open
1=alarm active if the contact is closed
0
1
-
-
EX16
Resource defined as thermal alarm for water pump 2
0=disabled
1=digital input 1
2=digital input 2
3=digital input 3
4=analog input 1 configured as digital input
5=analog input 2 configured as digital input
6=analog input 3 configured as digital input
7=analog input 4 configured as digital input
8=analog input 5 configured as digital input
9=analog input 6 configured as digital input
10=analog input 7 configured as digital input
0
10
-
-
EX17
Polarity for the resource defined as thermal alarm for water
pump 2
0=alarm active if the contact is open
1=alarm active if the contact is closed
0
1
-
-
EX18
Resource defined as thermal alarm for water pump 3
0=disabled
1=digital input 1
2=digital input 2
3=digital input 3
4=analog input 1 configured as digital input
5=analog input 2 configured as digital input
6=analog input 3 configured as digital input
7=analog input 4 configured as digital input
8=analog input 5 configured as digital input
9=analog input 6 configured as digital input
10=analog input 7 configured as digital input
0
10
-
-
EX19
Polarity for the resource defined as thermal alarm for water
pump 3
0=alarm active if the contact is open
1=alarm active if the contact is closed
0
1
-
-
EX20
Reserved for future use
-
-
-
-
EX21
Reserved for future use
-
-
-
-
EX22
Water pumps rotation selction
0=rotation considering the number of start-up
1=rotation considering the running hours
0
1
-
-
EX23
Regulation delay after water pumps power on
0
999
sec
-
EX24
Water pumps shared working time
0
250
sec
-
EX25
Time delay between water pumps rotations
0
999
x10 hur
-
SYSTEM PRESSURE SWITCH SETTINGS
EX26
Pressure switch enabling on expansion
0=not enabled
0
1
-
-