Dimensions
Liebert
®
CW
™
System Design Manual
34
Figure 4-11 Cabinet and floor-planning dimensions, upflow, CW106, CW114 with EC fans, front return
Chilled
Water
Model
Net Weight lb (kg)
Plenum Height Data, in. (mm)
Unit only
w/Plenum & Fans
Supply Air
Dimension A
CW106
1240 (562)
1827 (829)
Grille Discharge
22.75 (578)
CW114
1375 (624)
1962 (890)
Top Discharge
22.75 (578), 30 (762), 36 (914)
RETURN AIR GRILLE
SUPPLIED ON
UNITS WITH FRONT AIR RETURN
120"
3048mm
BASE
1"
25mm
33"
838mm
BASE
PROJECTION OF
DISPLAY BEZEL
122"
3099mm
OVERALL
76"
1930mm
UNIT
A
PLENUM
NOTE: DUCT FLANGES ON PLENUM
TOP FOR SUPPLY AIR DUCTING WHEN
SOLID PANEL PLENUM IS USED.
1"
25mm
76"
1930mm
79 1/4"
2013mm
EC FAN TERMINAL BOX
LEFT SIDE DETAIL VIEW WITHOUT
PLENUM OR EC FANS
FRONT AIR RETURN MODEL SHOWN
Note:
1. Shaded areas indicate a recommended
minimum CLEARANCE OF 36" (914mm) for
component access from the bottom of the unit
to the top of the plenum.
1
3/4"
19mm
35"
889mm
OVERALL
DPN003216
Pg. 1 Rev. 1
Summary of Contents for CW089
Page 2: ......
Page 8: ...Liebert CW System Design Manual vi ...
Page 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Page 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Page 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Page 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Page 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...