Customer-supplied Equipment and Ductwork
99
Liebert
®
CW
™
System Design Manual
Figure B-4 Liebert Air Economizer temperature and humidity sensor wiring
BOTH PO
SSIBLE
LOW V
OLTAGE
COMPA
RTMENT
S SHOW
N.
IDENTIF
Y WHICH
APPLIE
S
B
C
D
BOTH SENSORS
AND CABLES
ARE SHIPPED
IN BOXES
INSIDE ECONOMIZER
DETAIL D
CONNECT P67 ON THE
CONTROL BOARD
TO P66 ON THE
RETURN AIR T/H SENSOR
USING CABLE PROVIDED
SECURE RING TERMINAL
(FOR SENSOR CABLE SHIELD)
INTO BACK OF ELECTRIC BOX
(EARTH GROUND)
DETAIL C
CONNECT P66 ON THE
RETURN AIR T/H SENSOR
TO P67 ON THE CONTROL
BOARD USING CABLE
PROVIDED
DETAIL B
MOUNT OUTDOOR
AIR SENSOR
INSIDE OF OUTDOOR
AIR PLENUM
SECURE RING TERMINAL
(FOR SENSOR CABLE SHIELD)
INTO METAL DUCT
(EARTH GROUND)
CONNECT P66 ON THE
OUTDOOR AIR T/H SENSOR
TO P67 ON THE RETURN
AIR T/H SENSOR
USING CABLE PROVIDED
ROUTE CABLE THROUGH
CUSTOMER CREATED HOLE
IN PLENUM, THEN SEAL
OUTDOOR AIR
T/H SENSOR
RETURN AIR
T/H SENSOR
FRONT VIEW
RETURN AIR
T/H SENSOR
MOUNT RETURN AIR
T/H SENSOR INDOORS,
ABOVE UNIT RETURN
CONNECT P67 ON THE
RETURN AIR T/H SENSOR
TO P66 ON THE OUTDOOR
AIR T/H SENSOR
USING CABLE PROVIDED
OUTDOOR AIR
T/H SENSOR
(IDENTIFIED WITH
OUTDOOR LABEL)
DPN001449
Pg. 4 Rev. 3
Summary of Contents for CW089
Page 2: ......
Page 8: ...Liebert CW System Design Manual vi ...
Page 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Page 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Page 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Page 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Page 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...