Optional Configuration for Liebert CW Seismic Application
Liebert
®
CW
™
System Design Manual
86
Figure A-2 Anchor detail—Seismic anchorage rigid floor stand, downflow, CW026 – CW181
Model Number
Dimensions in. (mm)
Anchor
Size
A
B
C
D
CW026, CW038, CW041
46.5 (1181)
42.3 (1073)
3.0 (76)
4.0 (102)
1/2
CW051, CW060
70.5 (1791)
CW076, CW084
95.5 (2426)
4.0 (102)
6.0 (152)
CW089, CW106, CW114
118.5 (3010)
CW146, CW181
54.3 (1378)
6.0 (152)
8.0 (203)
Anchor bolt sized per Hilti Kwik Bolt TZ carbon and stainless in concrete, ICC ESR-1917.
Alternates are subject to review by Emerson or engineer of record.
ANCHOR DETA IL
TYPICAL 6 PLACES
*MIN. EMBEDMENT
*MIN. HOLE
DEPTH
*MIN. PAD
THICKNESS
FLOOR ANCHORING DIMENSIONS
1/8" (3mm)
FIELD WELDING OF UNIT TO FLOORSTAND
UNIT MUST BE WELDED TO FLOORSTAND TO MAINTAIN CERTIFICATION
ANSI B18.22.1
TYPE A, SERIES W PLAIN
WASHER REQUIRED AT
EACH ANCHOR LOCAITON
* SPECIFIED BY ENGINEER OF RECORD
A
A/2
1.0"
25mm
TYP.
B
3.5"
89mm
TYP.
1.8"
44mm
TYP.
2.8"
70mm
TYP.
C
C
D
D
C
C
H
5.6"
143mm
2.0"
51mm
2.5"
64mm
MIN. EDGE
DISTANCE
DPN003209
Pg. 3 Rev. 2
Summary of Contents for CW089
Page 2: ......
Page 8: ...Liebert CW System Design Manual vi ...
Page 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Page 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Page 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Page 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Page 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...