Dimensions
Liebert
®
CW
™
System Design Manual
32
4.3 Cabinet and Floor-planning
Dimensions—Upflow Models with EC Fans
Figure 4-9 Cabinet and floor-planning dimensions, upflow, CW026 – CW084 with EC fans, front air return
Plenum Height Data, in. (mm)
Supply Air
Dimension A
Grille Discharge
22.75 (578)
Top Discharge
22.75 (578), 30 (762), 36 (914)
Model
Dimensional Data, in. (mm)
Net Weight, lb (kg)
B
C
Unit Only
Unit
with Plenum and Fans
CW026
50 (1270)
48 (1219)
518 (235)
750 (340)
CW038
542 (246)
774 (351)
CW041
589 (267)
821 (372)
CW051
74 (1880)
72 (1829)
755 (342)
1118 (507)
CW060
827 (375)
1190 (540)
CW076
99 (2515)
97 (2464)
1141 (518)
1566 (710)
CW084
1239 (562)
1664 (755)
C
BASE
1"
25mm
33"
838mm
BASE
PROJECTION OF
DISPLAY BEZEL
B
OVERALL
35"
889mm
OVERALL
72"
1829mm
UNIT
A
PLENUM
NOTE: DUCT FLANGES ON PLENUM
TOP FOR SUPPLY AIR DUCTING WHEN
SOLID PANEL PLENUM IS USED.
1"
25mm
SHADED AREAS
INDICATE A RECOMMENDED
CLEARANCE OF 36" (914mm) BE
PROVIDED FOR COMPONENT
ACCESS AND FILTER REMOVAL. FOR
RECOMMENDED MINIMUM
CLEARANCE REFER TO THE
INSTALLATION MANUAL.
72"
1829mm
75 1/4"
1911mm
EC FAN TERMINAL BOX
3/4"
19mm
LEFT SIDE DETAIL VIEW WITHOUT
PLENUM OR EC FANS
RETURN AIR GRILLE
SUPPLIED ON
UNITS WITH FRONT RETURN
FRONT AIR RETURN MODEL SHOWN
DPN003215
Pg. 1 Rev. 1
Summary of Contents for CW089
Page 2: ......
Page 8: ...Liebert CW System Design Manual vi ...
Page 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Page 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Page 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Page 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Page 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...