Anchor and Load Requirements of Seismic Installation
87
Liebert
®
CW
™
System Design Manual
Figure A-3 Seismic certification as tested connection detail, upflow, CW114 and CW181
Model #
Weld Length, in. (mm)
Number of
Supports
Floor-stand
Height, in. (mm)
A
B
C
CS026DCS
3 (76.2)
4 (101.6)
4
12 (304.8)
CW114DC1
4 (101.6)
6 (152.4)
6
36 (914.4)
CW181DC1
6 (152.4)
8 (203.2)
F
DETAIL F
1/8"
FASTENED TO THE SHAKE TABLE
USING 1/2" A325 BOLTS
6.0"
152mm
6 PLACES
FRONT
PLAN VIEW OF ATTACHMENT ANGLES
FRONT
PLAN VIEW OF UNIT ATTACHMENT
G
DETAIL G
B
2 PLACES
A
A
A
A
4 PLACES
B
TOTAL 'C' - 7/8" GRADE 7 THREADED RODS WITH
1/8" THICK NEOPRENE PAD.
FLOORSTAND SUPPORTED LIBERT CW ANCHORAGE
FLOOR MOUNTED LIBERT CW ANCHORAGE (CW114UCS)
DPN003209
Pg. 11 Rev. 2