Table 2-4
Motor size required to deliver rated airflow, models with forward-curved blowers
External Static
Pressure
0.2"
0.4"
0.6"
0.8"
1.0"
1.2"
1.4"
Model
Rated Airflow
CFM (l/s)
Motor Size, hp
026
5050 (2383)
3
5
5
5
5
5
5
038
5850 (2761)
5
5
5
—
—
—
041
5750 (2714)
5
—
—
—
—
—
—
051
9150 (4318)
7.5
7.5
—
—
—
—
—
060
8900 (4200)
7.5
7.5
—
—
—
—
—
076
12100 (5711)
10
15
15
15
15
—
—
084
11650 (5498)
10
15
15
15
15
—
—
106
17100 (8070)
15
15
15
15
15
—
—
114
16500 (7787)
15
15
15
15
—
—
—
*
Delivered airflow is less than rated airflow
Table 2-5
Maximum airflow with maximum motor size at listed static pressure,
models with forward-curved blowers
External Static
Pressure
0.2"
0.4"
0.6"
0.8"
1.0"
1.2"
1.4"
Model
Rated
Airflow
CFM (l/s)
Airflow, CFM (l/s)
026
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
5050
(2383)
038
5850
(2761)
5850
(2761)
5850
(2761)
5850
(2761)
5750
(2714)
5600
(2643)
5450
(2572)
5350
(2525)
041
5750
(2714)
5750
(2714)
5750
(2714)
5600
(2643)
5450
(2572)
5350
(2525)
—
—
051
9150
(4318)
9150
(4318)
9150
(4318)
9100
(4295)
8900
(4200)
8700
(4106)
8550
(4035)
8350
(3941)
060
8900
(4200)
8900
(4200)
8900
(4200)
8750
(4130)
8550
(4035)
8400
(3964)
8200
(3870)
8050
(3799)
076
12100
(5711)
12100
(5711)
12100
(5711)
12100
(5711)
12100
(5711)
12100
(5711)
11600
(5475)
11000
(5191)
084
11650
(5498)
11650
(5498)
11650
(5498)
11650
(5498)
11650
(5498)
11650
(5498)
11400
(5380)
NA
106
17100
(8070)
17100
(8070)
17100
(8070)
17100
(8070)
17100
(8070)
17100
(8070)
16400
(7740)
16100
(7598)
114
16500
(7787)
16500
(7787)
16500
(7787)
16500
(7787)
16500
(7787)
16100
—
—
Summary of Contents for CW089
Page 2: ......
Page 8: ...Liebert CW System Design Manual vi ...
Page 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Page 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Page 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Page 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Page 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...