Table A-3
Upflow Liebert CW models on floor stand with 36" plenum, CW026-CW114
Model Number
Floor
Stand
Height
Operating
Mass *
Restraint
Locations
Maximum Load
per Anchor
Maximum Load
per Location
Anchors
per
Location
Tension
Shear
Tension
Shear
CW026-CW041UCS
24
1163.1
4
633.4
160.2
1329.8
320.6
2
48
1204.8
4
868.7
165.6
1822.6
331.6
2
CW051-CW060UCS
24
1578.4
4
748.4
226.4
1646
452.6
2
48
1628.6
4
1020.2
233
2240.2
465.8
2
CW076-CW084UCS
24
1936.1
6
613.1
184.6
1343.8
369.3
2
48
2005.3
6
840.1
190.6
1838.4
381.5
2
CW089-CW114UCS
24
2589.5
6
816.4
250.6
1818.1
501.2
2
48
2667.6
6
1103.4
257.4
2452.7
514.9
2
*
Operating mass includes the operating water volume, floor stand and plenum.
Table A-4
Downflow Liebert CW models on floor stand without plenum, CW026-CW081
Model Number
Operating
Mass *
Restraint
Locations
Maximum Load
per Anchor
Maximum Load
per Location
Anchors
per Location
Tension
Shear
Tension
Shear
CW026-CW041DC1
953
4
402.4
134.7
845.1
269.7
2
994
4
593.9
140.1
1246.2
280.6
2
CW051CW060DC1
1318
4
466.7
181.6 1028.8
363.2
2
1368
4
692.7
188.2
1523
376.4
2
CW076-CW084DC1
1621
6
385.6
153.9
847
308
2
1690
6
574.6
160
1258.9
320.2
2
CW089-CW114DC1
2255
6
539
211.5
1203.2
423
2
2333
6
788
218.3
1753.9
436.7
2
CW146-CW181DC1**
3136
6
943
284.7
2017.7
569.6
2
3237
6
1233.8
294.5
2636.9
589.2
2
*
Operating mass includes the operating water volume, floor stand and plenum.
** 18" filter plenum only.
Table A-5
Upflow Liebert CW models on floor stand without plenum, CW026-CW114
Model Number
Operating
Mass*
Restraint
Locations
Maximum Load
per Anchor
Maximum Load
per Location
Anchors
per Location
Tension
Shear
Tension
Shear
CW026-CW041UCS
1008
4
481.1
139.8
1010.3
279.8
2
1049
4
684.1
145.2
1435.4
290.8
2
CW051-CW060UCS
1358
4
566.9
193.8
1248
387.5
2
1408
4
799.9
200.4
1757.5
400.7
2
CW076-CW084UCS
1676
6
465.5
159.7
1021.3
319.5
2
1745
6
661.2
165.7
1447.6
331.7
2
CW089-CW114UCS
2255
6
632.7
220.4
1410.3
440.7
2
2333
6
881.8
227.2
1961
454.4
2
*
Operating mass includes the operating water volume, floor stand and plenum.
Summary of Contents for CW089
Page 2: ......
Page 8: ...Liebert CW System Design Manual vi ...
Page 10: ...Liebert CW System Design Manual vi Page intentionally left blank ...
Page 18: ...Nomenclature and Components Liebert CW System Design Manual 8 Page intentionally left blank ...
Page 62: ...Dimensions Liebert CW System Design Manual 52 Page intentionally left blank ...
Page 76: ...Piping Liebert CW System Design Manual 66 Page intentionally left blank ...
Page 90: ...Electrical Field Connections Liebert CW System Design Manual 80 Page intentionally left blank ...