Hand-Held Terminal
Gateway Board Mounting • 3
2
Gateway Board
Mounting
The Gateway is typically mounted in the same area as
the site controller, near the controller’s 16AI, 8RO, and
other RS485 Network peripherals. The Gateway is de-
signed to fit into a standard 3" snap track (supplied with the
board) or may be mounted in a panel or on stand-offs. Fol-
low the dimensions in
for panel mounting.
The Gateway should be mounted in an environment
with ambient temperature between -40°F and 150°F, with a
non-condensing relative humidity between 5% and 95%.
Gateway boards are not supplied with an enclosure but
come with a snap-track for easy installation. The insulation
sheet and I/O board must be removed from the track before
the track is mounted. The snap-track is mounted using the
0.1875” mounting slots.
shows this installation
procedure.
Figure 2-1
- Gateway Board Mounting Dimensions
Figure 2-2
- Snap-Track Installation