21
Installation
Power Supply Requirements
The examples below show AC power connections for single
phase and three phase drives. These examples are shown for
reference only. Local electrical codes should be consulted before
installation.
Warning
The Protective Earth (PE) wire connection is mandatory for
human safety and proper operation. This connection must
not be fused or interrupted by any means. Failure to follow
proper PE wiring can cause death or serious injury.
The Eb-202, Eb-203 and Eb-205 drives require 42 to 264 VAC
single-phase power. An Epsilon drive can be connected to any
pair of power phases on a 1 Ø or 3 Ø power source that is
grounded as shown in the following diagrams.
If using an APS Logic Power input and the Low DC Bus fault
is disabled, minimum supply voltage to an Epsilon can be
reduced to 15 VAC on the AC inputs or 24 VDC on the Bus +/-
connections.
Note
The maximum voltage applied to the drive terminals must
not exceed 264 VAC phase to phase and phase to PE ground.
This can be accomplished by referencing the AC supply to
earth ground.
Caution
Do not connect or disconnect the AC power by inserting or
removing the AC power connector. Using the connector in
this manner, even once, will damage the connector, making
it unusable.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Summary of Contents for Control Techniques Epsilon Eb-202
Page 21: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Page 25: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Page 133: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...