Installation, Operation and Maintenance Manual
MAN-02-10-93-0700-EN Rev. 0
May 2019
11
Section 5: Local Display Module
Local Display Module
Table 3.
Alarm List
Alarm
Definition
Details
CE
Communication Error
Lost communication with the Remote Display Module (RDM)
when configured.
SA
Stall Alarm
Actuator failed to move within 8 seconds after commanded by
either local or remote controls.
LE
Local ESD
Hardwired Local Emergency Shut Down is active.
PH
Phase Alarm
Loss of one phase when configured for 3-Phase.
EF
Encoder Failed
Failure of either the position or torque encoders.
AF
Actuator Failed
A fault is detected by hardware electronics fault monitor.
This is a non-recoverable condition that requires actuator service.
OL
Motor Overload
Motor thermals or motor overload relay has tripped.
LC
Lost Control Voltage
Loss of power to the motor control circuits. The control voltage
supply has an automatic resetting fuse.
NOTE:
Over torque alarm is displayed by dedicated LED. See Operational Display section above.