20
Installation, Operation and Maintenance Manual
MAN-02-10-93-0700-EN Rev. 0
May 2019
Section 7: Field Setup Using Local Controls
Field Setup Using Local Controls
Section 7: Field Setup Using Local Controls
Use the Local Control (left) knob and Selector (right) knob to enter setup mode and to
execute Setup functions. The table below (see Table 5) outlines the knob functions for
Setup mode.
To access the Field SETUP mode of operation ensure the Selector Knob is placed in the
OFF (Stop) position. Once set, rotate the Control Knob to the “UP” & then to the “DOWN”
position in right to left succession three times. Keep the knob in each position for at least
½ second but not more than 3 seconds. The display module will flash the (3) amber LOR
selector LED’s when the SETUP mode is enabled.
Figure 15
Table 5.
Selector / Control Knob Setup Function
Selector Knob (right)
Setup Function
Results
OFF (Stop) [return position] neutral position
Allows entry to SETUP mode.
Completes NEXT, or BACK entry
cycle, except when knob is held for
scrolling through various menus.
Clockwise (REMOTE) (Auto)
NEXT
Advances to the next menu item.
Displayed data is accepted.
Counter-clockwise (LOCAL)
(Hand)
BACK
Backs up to the last menu item.
Control Knob (left)
Setup Function
Results
Spring Return to Center
neutral position
Completes UP or Down entry Cycle
except when knob is held for
continuous data entry update.
Clockwise (CLOSE)
UP
Increments displayed data.
Counter-clockwise (OPEN) DOWN
Decrements displayed data.