30
Installation, Operation and Maintenance Manual
MAN-02-10-93-0700-EN Rev. 0
May 2019
Section 9: Remote Network Control
Remote Network Control
9.3
Profibus DP Reduntant Networks with Redcom
The MPA uses CAM20 to convert between Mosbus RTU and Profibus DP. This section
describes the data mapping between the Profibus DP host and MPA Modbus map.
The mapping allows the Profibus DP host to control the Flow Selector and monitor the
actuator status. The control information is mapped directly to words in the Profibus Output
data and status information is mapped directly to words in the Profibus Input data.
Table 11.
Output Data
Location
Bit
Word Byte
7
6
5
4
3
2
1
0
1
1
Not
used
Not used
1
2
Not
used
Not
used
Not
used
Not
used
Host ESD
Com-
mand
Go to
Next
Point
Not
used
Not
used
2
3
Flow Selector Port Position Setpoint (0-7) Single Bit
2
4
3
5
Not used
3
6
Table 12.
Input Data
Location
Bit
Word Byte
7
6
5
4
3
2
1
0
1
1
Not
used
Not
used
Not
used
Not
used
Not used
Actuator
Fail Alarm
1
2
Not used
Not
used
Not
used
Host ESD
Monitor
Not used
2
3
Unit
Alarm
Not used
Local ESD
Alarm
Phase
Monitor
Alarm
Motor
Thermal
Alarm
Power
Monitor
Alarm
Flow
Selec-
tor Stall
Alarm
2
4
Stopped
Between
Ports
Over
Torque
Alarm
Selector
Remote /
Auto
Selector
Local /
Manual
Wrong
Direction
Alarm
Flow
Selector
Moving
Within 2
degrees
of port
Within 1
degree of
port
3
5
Flow Selector Position (0-7) Single Bit
3
6
4
7
Torque (0-99%)
4
8
5
9
Not used
5
10
6
11
Not used
6
12