Installation, Operation and Maintenance Manual
MAN-02-10-93-0700-EN Rev. 0
May 2019
15
Section 6: Field Setup Using MPA Config Software
Field Setup Using MPA Config Software
6.3
Selecting New Home Port
(HP command using Control Knob setup)
The User may select any port as the new “Home Port” in the field. When a new home
port is selected, the new home port is identified as Port 0 or 8 and the MPA reassigns all
other port numbers (1-7) in a counterclockwise sequence around the MPFS. The MPA
recalculates the exact calibrated port position based on factory calibration values so no
accuracy is lost.
To select a new home port, click on the “Set Home Port” button shown in Figure 11.
The Pop-Up shown in Figure 9 will appear. Enter the new home port number 1-7 relative to
the factory calibrated port assignments and click “Enter”.
Figure 11
NOTE:
When a new home port is selected, it must be a port without piping connected and
must be fitted with a blind cover to allow for future seal inspection and visual port
alignment. Selecting a new home port will cause the MPA to recalculate all calibration
parameters based on the factory calibration and store the new values to EEPROM.